WSM6 Manual
Document Ref: UM-8270-000
Issue: A Rev 0
Section 4
22
To operate the vent valve:
WARNINGS
Do not stand directly inline with the WSM6 end-cap. Toxic gases or corrosive liquids
may be forcibly expelled due to serious battery failure.
1.
Screw an M4 bolt into the Pressure Relief Vent Valve.
2.
Slowly pull the M3 bolt to withdraw the vent valve.
4.2
Charge the Battery
The standard WSM6 is fitted with Nickel Metal Hydride rechargeable battery. The Type 7972-000-
04 Charger will charge the batteries in approximately 4 hours.
The WSM6 includes special circuitry to monitor the battery pack during charging. This safety
feature makes sure the battery cannot be over-charged in normal use.
The WSM6 should always be switched off when not in use to minimise entering into a deep
discharge state. In this state it is possible for some cells to drop to near zero voltage or even
reverse the voltage of their terminals.
There are four states of charge for the battery, each requiring different charging methods.
For a battery that is partially discharged proceed with the charging instructions in this section. For
any other charge condition of the battery refer to
Section 6.3 - WSM6 Battery Charging
.
To charge the battery:
CAUTION
The WSM6 battery pack must only be charged using the Sonardyne Type 7972-000-04
comms/charger unit and matching charger PSU.
1.
Operate the Pressure Relief Vent Valve – refer to
Section 4.1
2.
Check the ambient temperature is between 10 and 40°C. The battery will not accept charge
outside these limits.
3.
Check the WSM6 ON/OFF switch is set to OFF (refer to
4.
Unscrew and remove the protective cap from the Connector End-Cap connection point.
5.
Connect the Type 7972-000-04 WSM6 comms/charger to the WSM charger PSU using a
2.1mm power socket. The PSU accepts a standard IEC power lead.
October 2011