![SOMFY Animeo 1870452 Manual Download Page 35](http://html.mh-extra.com/html/somfy/animeo-1870452/animeo-1870452_manual_1317508035.webp)
animeo KNX 4 DC Motor Controller
28.02.2019
WM 24 V DC
2019 Somfy Activités SA
Ref. 5147817A
35/56
6.7.4 Contact type input B
Default value:
0
Selection options:
0
– 255
With this parameter the value is set which is transmitted with a rising edge at the local input B.
6.7.5 Contact B value on rising edge (0-255)
Default value:
Normally open
Selection options:
Normally open
Normally closed
With this parameter it is defined which contact type is at the local input B.
Normally open: The contact at the local input is activated closed and not activated opened.
Normally closed: The contact at the local input is activated opened and not activated closed.
6.8
Menu index card “Binary inputs – Dimming”
6.8.1 Basic Function
Selected option:
Dimming
6.8.2 Long operation (dimming) after
Default value:
0.5 seconds
Selection options:
0.3 - 5.0 seconds
This parameter defines the activity time of the corresponding push button which makes a distinction between
the sending of a switching telegram and a dimming telegram. If the time, for example, is parameterized on
0.5 seconds, a dimming telegram is generated only after a press longer than 0.5 seconds is made. With a
pressing shorter than 0.5 seconds a switch telegram is generated.
6.8.3 Input A/B
Default value:
On/Off
Selection options:
On/Off
Toggle/Toggle
This parameter defines the value which is transmitted with a short pressing of the corresponding input.