Solplanet ASW10000-S Quick Installation Manual Download Page 1

 

   

Quick Installation Guide 

 

ASW6000-S / ASW8000-S/ASW10000-S 

       

         

 

 

1. The contents of this document may be updated due to product upgrades or other reasons. Unless     
    otherwise specified, this document only works as guide. All statements, information and   

suggestions in this document do not constitute any guarantee. 

2. This product can only be installed, commissioned, operated and maintained by technicians who 
    have carefully read and fully understood the user manual. 
3. This product must only be connected with PV modules of protection class II (in accordance with 
    IEC 61730, application class A). PV modules with a high capacitance to ground must only be used 
   

if their capacity does not exceed 1μF.

 Do not connect any sources of energy other than PV   

    modules to the product. 
4. When exposed to sunlight, the PV modules generate dangerous high DC voltages which is present 
    in the DC cable conductors and live components. Touching live DC cable conductors and live 
    components can result in lethal injuries due to electric shock. 
5. All components must remain within their permitted operating ranges at all times. 
6. The product complies with Electromagnetic compatibility 2014/30/EU, Low Voltage Directive   
    2014/35/EU and Radio Equipment Directive 2014/53/EU. 
 
 

 

1. Ensure that the inverter is installed out of the reach of children. 
2. To ensure best operating status and prolonged service life, the   

ambient temperature of the location should be 

40

°

C. 

3. To avoid direct sunlight, rain, snow, pooling of water on the inverter, it is 

suggested to mount the inverter in places which are shaded during the majority of       
the day or to install an external cover that provides shade for the inverter. 
Do not place a cover directly on top of the inverter. 

4. The mounting condition must be suitable for the weight and size of the inverter. The inverter is suitable 

to be mounted on a solid wall that is vertical or tilted backwards 

(Max. 15°). It is not recommended to

 

install the inverter on walls made of plasterboards or similar materials. The inverter may emit noise   

during operation. 

 
 
 

 

5. To ensure adequate heat dissipation, the recommended clearances between the   
    inverter and other objects are shown in the image to the right: 

 
 

 

1. 

Use a Φ1

0mm bit to drill 2 holes at a depth of about 70mm according to the location of the wall 

mounting bracket. (Figure A) 

2. Insert the wall plugs into the wall and fix the mounting bracket to the wall by inserting two Screws     

(SW10). (Figure B) 

3.

 

Push the inverter to wall bracket and hook it. Ensure the two right- and left-hand keys on the outer ribs 

of the inverter must be hooked into the respective keyways in the wall mounting bracket. (Figure C) 

4. Ensure that the inverter is securely in place, then secure the inverter to the mounting bracket on both 

sides using two M5 screws. Screwdrivertype:PH2, torque:2.5Nm. (Figure D) 

                         

 

 

 
 

 

 
 

 

 
 
 

                                                       

 
 

 

 
 
 
 
 
 
 
 
1. Strip the AC cable as shown in the figure

and crimp the copper wire to the appropriate cord end 

terminal (according to DIN 46228-4, provided by the customer). 

 
 

 
 
 

Object 

Description 

Value 

External diameter 

14-20mm 

Copper conductor cross-section 

6-16mm

2

 

Stripping length of the insulated conductors 

16mm 

Stripping length of the cable outer sheath 

46mm 

Note: the PE conductor is at least 5mm longer than the L and N conductors. 

 
2. Insert the PE, N and L conductor into the cord end terminal, insert them into the corresponding 

terminals of the AC connector in the order as shown, and tighten the screws by the hex key with a 
suggested torque of 2.0 Nm. 

 

 
 
 
 
 
3.

 

Secure the connector body assemble to the connector, then tighten the nut cap to the connector 

body. 

 
 
 

 
 
 
 

 
4. Insert the AC connector plug into the output socket of AC connector corresponding to the inverter and   

tighten them.   

 
 
 
 

 

 
5. If required, you can connect a second protective conductor as equipotential bonding. 
     
 
 
 
 
 
 
 
 
 
 
6. if required

you can use a slot type screwdriver to disassemble the AC connector plug from the inverter. 

 
 
 
 
 
 
 
 
 
 
 
 

Object 

Description 

M5 screw 

Screwdriver type: PH2, torque: 2.5Nm 

OT terminal lug 

Customer provided, type: M5 

Grounding cable 

Copper conductor cross-section: 6-16mm

2

 

 

 

 

 

Figure A 
 

Figure B 
 

I. Safety Instruction 

II. Mounting environment 

 

IV. Inverter's mounting 

Figure C 
 

Figure D 
 

V. AC connection 

All electrical installations must be done in accordance with all local and national rules. 

Ensure that all DC switches and AC circuit breakers have been disconnected and all power sources 

have been electrically isolated before any electrical terminations have been made.    High voltages 
produced by the inverter may lead to electrical shock. 

In accordance with safety regulations, the inverter needs be correctly grounded. When a poor   

ground connection (PE) occurs, the inverter will report PE grounding error. Please check and ensure   
that the inverter is grounded firmly or contact AISWEI service. 
 
 

 

     

 

 