Brick Veneer or Frame Wall Construction.

See CAUTION under General Instructions. 

Cut or build

rough opening large enough to allow a framed, finished
opening 1

7

-inches high and 2

6

1

/

8

-inches wide. When case

is properly positioned in opening, secure it to framing
material with nails or screws driven through holes in sides
of outer case (shim case and predrill holes before
securing).

Framing

lumber

2

6

1

/

8

"

17

"

Framed/Finished Opening

(brick veneer or frame wall construction)

Placement of Outer Case in Opening

Place outer case in opening, flush against one side of
opening. Use carpenter’s level and ensure case is level
from side to side and has a 

3

/

8

-inch slope from front to back

(back of case must be 

3

/

8

-inch lower than front to ensure

proper condensate drainage). If needed, use shims to level
case (from side to side) and to obtain proper back slope.
Front of case must project ¾-inch (minimum) beyond
inside wall in order to attach air conditioner front frame. If
framing indoor side of opening with wood molding (or other
decorative material), extend outer case ¾-inch beyond
molding.

When case is properly positioned in opening, use wood
shims to fill any gaps between case and finished opening,
especially in area where case will be secured to opening.

Take care not to warp or distort case when installing
shims

. For condensate drainage, install drainage cup in

drain hole on baseplate of case.

Caulk all
sides

Lintel and
flashing
(if required)

Outercase must project
a minimum ¾" 
beyond inside wall
or molding to attach front frame

9

 

"

I

nstall case

with 

3

/

8

"

slope to outside
for condensate
drainage

Front of outer case
to side air louvers

Optional
molding 
(not provided)

Installed Case

(brick veneer or frame wall construction shown)

Installation in Wall Thicker Than 9-inches

The side louvers in outer case provide ventilation to air
conditioner compressor and fan motor and must not be
blocked. When installing unit in a wall over 9-inches
thick, provisions must be made in wall opening to ensure
free air flow to the side louvers. This can be accomplished
by chamfering the vertical portions of the outside opening
as shown.
Ventilation louvers on top of case must not be obstructed.
Do not attempt to install unit in walls thicker than
11

2/5

-inches.

Front of 
outercase

4" 4"

Side air 
louvers
(both sides)

¾" minimum
projection

11

2/5

"

9"

3

4

"

2

6

"

Chamfering Walls Thicker Than 9-inches

16

Summary of Contents for KC-45H

Page 1: ...BTU Room Air Conditioner with Heat Pump OPERATING AND INSTALLATION MANUAL Model KC 45H Thank you for selecting Soleus Air To ensure proper operation please read this manual and keep it for future refe...

Page 2: ...UCTIONS 6 11 OPERATING CONTROLS 12 BEFORE CALLING SERVICE 13 WHEN SERVICE IS REQUIRED 14 ANY QUESTIONS 14 THROUGH THE WALL INSTALLATION INSTRUCTIONS 15 16 SPECIFICATION 17 WARRANTY 18 Thank you for se...

Page 3: ...arranty Service line at 1 888 8 SOLEUS If your problem cannot be resolved by phone contact an authorized Soleus Air brand servicer Contact and service will be at your expense Safety Information Be sur...

Page 4: ...appliance or light fixture ReceptacleWiring Receptacle wiring must be of adequate size for unit Refer to unit identification plate for exact power requirements Minimum size of wiring based on power r...

Page 5: ...separately Through the wallinstallationinstructionsareincluded with the outer case These models can be adapted to window installation by purchasing an optional mount ing kit RoomHeatPumps Heatpumpswo...

Page 6: ...lter Cleaning A dirty air filter reduces operating efficiency of unit Filter should be inspected at least once every week during opera tion Cleanfilterwithvacuumcleanerorwashinwarmwater and mild deter...

Page 7: ...outdoor coil surface This is the sound of water you hear during normal operation The water quickly evaporates on this warm surface and improves the efficiency of your air conditioner In normal condit...

Page 8: ...properly grounded 3 prong wall outlet Some models require 230 208 volt a c protected with a time delay fuse or circuit breaker These models should be installed on their own single branch circuit for...

Page 9: ...7 Installation Instruction Continuous...

Page 10: ...piece of wood to the stool WOOD PIECES WIDTH 2 LENGTH Long enough to fit inside the window frame THICKNESS To determine the thickness place a piece of wood on the stool to make it 1 2 higher than the...

Page 11: ...OW A Carefully slide the case into the window and center the case Lower the window behind the top mounting rail Pull the bottom of the case forward so that the bottom mounting rail is tight against th...

Page 12: ...weak or if the weight of the air conditioner falls between the studs in the wall F Extend the left and right accordion panels to the vertical window sashes Drill pilot holes and attach the top and bot...

Page 13: ...bottom corners and pull it forward Unhook it from its top hinges and set it aside F Using the tab pull up slightly on the filter to release it and pull it down and out 8 INSTALL THE AIR CONDITIONER IN...

Page 14: ...GH HEAT Filters and circulates room air with the fan running continuously on high speed Also heats while the compressor or electric heater is running Select this setting for maximum air circulation an...

Page 15: ...ature Control to cooler setting For heating turn Temperature Control to warmer setting NOISY UNIT Loose front on mounting assembly Weak building construction Water hitting fan blade Unit oversized for...

Page 16: ...quent failure of unit voids warranty Warranty details are contained in warranty certificate enclosed with unit Keep accurate records of service calls including what was done servicer s name and date o...

Page 17: ...m side to side Use wood shims between sides of case and finished opening especially where case is secured to opening to prevent warping or distorting Check installed case for distortion using carpente...

Page 18: ...se is properly positioned in opening use wood shims to fill any gaps between case and finished opening especially in area where case will be secured to opening Take care not to warp or distort case wh...

Page 19: ...e Highside 340 P S I Cooling AMPS 9 7 8 9 Cooling Watts 1955 2000 Cooling EER 9 0 Heating AMPS 8 8 8 3 Heating Watts 1790 1850 Heating EER 9 2 Electric Heat AMPS 15 6 16 Electric Heat Watts 3600 Air F...

Page 20: ...ect accident incorrect power line voltage fire flood or other Acts of God or normal wear and tear Warranty service must be performed by a qualified HVAC contractor Soleus maintains a centralized servi...