Inspect the exhaust system components for cranks, leaks and corrosion.
EXHAUST SYSTEM INSPECTION POINTS
1.
Check the hoses for softness, cranks or dents. Replace the hoses as needed.
2.
Check for corroded or broken metal parts and replace them as needed.
3.
Check for loose, corroded or missing clamps. Tighten or replace the hose clamps
and/or hangers as needed.
4.
Check that the exhaust outlet is unobstructed.
5.
Visually inspect the exhaust system for exhaust leaks. Check for carbon or soot residue
on exhaust components. Carbon and soot residue indicates an exhaust leak. Seal
leaks as needed.
5.8. Electrical System
BATTERY
The minimum recommended capacity is from 100Ah. However, this value serves as a
general reference since it relates to the maximum intensity it can offer for starting the generator
set.
CIRCUIT PROTECTION
AC Breaker interrupts the genset output in the event of an overload or short
circuit. It is located in front panel as is showed in the section 10.
MAINTENANCE TASK. STARTER MOTOR INSPECTION
1.
Check if there is any impurity in pinion teeth.
2.
Make sure that the pinion shaft turns freely when turned
in the direction of driving (clockwise) and it is locked
when turned in the opposite direction. If not, replace
the overrunning clutch.
Genset model
Battery capacity (Ah)
85 GT/GTC - 100
GTA/GTAC - 115
GT/GTC - 120
GTA/GTAC
100
Genset model
Intensity (A)
85 GT/GTC (400/230V)
100
85 GT/GTC (230V)
180
100 GTA/GTAC (480/277V)
100
100 GTA/GTAC (240V)
200
115 GT/GTC (400/230V)
135
115 GT/GTC (230V)
240
120 GTA/GTAC (480/277V)
125
120 GTA/GTAC (240V)
240