background image

Step 3

:

Step 1: Using the bracket as a guide, mark the positions of the twelve holes.

II

- Position the top side of the inverter on the small hook of the bracket.
- Position the bottom of the inverter to lean on the bracket.
- Press the inverter slightly towards the hole to install it  rmly.

A1

User Manual x1

Warranty Card x1

A1-Hybrid 6.0KW- 8.6KW

Quick Installation Guide x1

Wi-Fi Module x1

I

III

Grounded bus-bar

IV

- The A1-Hybrid series inverter can be connected with PV modules in series with 2MPPTs for 6.0kW, 3 MPPTs for 7.0kW and 7.6kW, and 4 MPPTs for 8.6kW.

For wiring method,  refer to Section III.

PV Connection

Grid Connection

For wiring method, refer to Section III.

2 L-lines and 1 N-line connect to the Grid terminal through one port.

VI

BMS Cable Connection

For wiring method, refer to Section III.

1 CAT5 network cable  connects to the BMS terminal on the communication board.

Electrical Cable Connection

1 positive-line and 1 negative-line connect to BAT terminal through one port.

TRIPLE

POWER

TRIPLE

POWER

TRIPLE

POWER

+_

+ _

+ _

+ _

+

_

Grounded busbar

Batter

y Break

er

                                        

V

- The A1-Hybrid Series inverter can deliver output power through the load port when there is an outage. 
- An autotransformer must be connected to the inverter if a user wants to use this function.
- User should select appropriate critical loads to connect to the load port. Read the user manual carefully before 
   selecting critical loads requirements.

2 L-lines and 1 N-line through one port;
2 L-lines and 1 N-line connect  to LOAD terminal through one port.

Load Connection

2 L-lines and 1 N-line through one port;
2 L-lines and 1 N-line connect to TXS terminal through one port.

Auto-Transformer  Connection

For wiring method, refer to Section III.

Load Connection

L1   N   L2

LOAD

Auto-Transformer  Connection

L1 N L2 

TXS

Meter x1  
  CT x2

Inverter x1

Bracket x1

(for mounting)

Expansion Tube x12

(for mounting)

Expansion Screw x12

(for mounting)

3 PIN Terminal x1
2 PIN Terminal x1

Cord End Terminal

8.6KW x19; 7.6KW x17
7.0KW x17; 6.0KW x15

2-pole, 40A 120/240 VAC, 10kA

Grid Breaker Requirements

A1 Hybrid-6.0-US

Inverter Model

Recommended AC Branch Protection

A1 Hybrid-7.0/7.6-US

2-pole, 35A 120/240 VAC, 10kA

2-pole, 45A 120/240 VAC, 10kA

A1 Hybrid-8.6-US

Required Torque

Permitted Wire Size

Plug-in

8AWG,600V,194

/90

 for A1 Hybrid-6.0/7.0-US

6AWG,600V,194

/90

 for A1 Hybrid-7.6/8.6-US

120V/240V Split-phase

L1, N, L2

Battery Breaker Requirements

Recommended DC Branch Protection

35A, 600Vdc, 35kA

             Terminal: Rj45, 8

-

conductor    

Cable: CAT5 non

-

crossover network cable

Cable Requirement

15

.

75 in

/400mm

11

.

81 in

/300mm

11

.

81

in

/300mm

11

.

81

in

/300mm

29

.

53 in

/750mm

- Drill holes (depth of at least 2.36in/60mm) with a φ10 drill.

Step 2

:

- Mount the bracket and tighten the expansion tubes. Then screw the expansion screws.

Part

Required Torque

Mounting Expansion Screw (x12) 

92 lbf-in

Required Torque

Permitted Wire Size

Plug-in

8AWG,600V,194

/90

 for A1 Hybrid-6.0/7.0-US

6AWG,600V,194

/90

 for A1 Hybrid-7.6/8.6-US

2-pole, 40A 120/240 VAC, 10kA

Load Breaker Requirements

A1 Hybrid-6.0-US

Inverter Model

Recommended AC Branch Protection

A1 Hybrid-7.0/7.6-US

2-pole, 35A 120/240VAC, 10kA

Manual Bypass Breaker Requirements (optional)

A1 Hybrid-6.0-US

Inverter Model

Recommended AC Branch Protection

A1 Hybrid-7.0/7.6-US

double-pole double-throw
120/240VAC, 40A, 10kA

double-pole double-throw
120/240VAC, 35A, 10kA

2-pole, 45A 120/240 VAC, 10kA

A1 Hybrid-8.6-US

A1 Hybrid-8.6-US

double-pole double-throw
120/240VAC, 45A, 10kA

Step 1: Turn the DC switch to the  “OFF” position.  Remove the 8 cover screws, then remove the
             cover.

Step 2: The conduit plugs (circled in blue) should be removed by the operator before 
             connecting the wires.

Step 3: Operator should use the standard size conduit which must fit the holes on the bottom
           of the inverter. Conduit fittings must be watertight.

DC Switch

Max. 1.4 lbf- in

Max. 23 lbf- in

1G Waterproof Plugs  x8

 3/4G Waterproof Plugs  x3 

1G

3/4G

1G

1G

1G

1G

1G

3/4G

3/4G

1G

Conduit

Wirings

Conduit

0.47in/12mm

Wirings

Step 4:

4.1 Choose the appropriate wire according to the specific connection.
4.2 Remove 0.47in/12mm of the insulation from the end of the DC wire (the AC wire 
      shall be removed by 0.71 in/18mm).
4.3 Insert the end of wires into the Cord End Terminal, and then use the crimping 
pliers to crimp the Cord End Terminal tightly (the shape will be square).
4.4 Using the slot screwdriver to compress the orange button of the terminals, 
insert the stripped wires into terminal and ensure that all conductor strands are 
captured in the terminal.
4.5 Loosen the slot screwdriver.

Slot Screwdriver Type

SL 3

Removing Wiring Box Cover Screw Torque

Removing Conduit Plug Torque

Reviews: