16 Messages
15.3 Refrigerant testing obligation
In accordance with the
F-Gas Regulation
(EU Regu-
lation 517/2014, in effect from 01/01/2015), a regular
leak test of the refrigerant circuit is required for air-to-
water heat pumps.
This test is based on the CO
2
equivalent of the ref-
rigerant used.
The heat pump
vamp
air
is filled with the refrigerant
R410A (hermetic system). The greenhouse potential
of 1 kg R410A corresponds to 2088 kg CO
2
-equi-
valent.
An annual refrigerant test obligation applies from 10
tonnes CO
2
-equivalent.
Calculation for vamp
air
K 08 and K 10
Refrigerant quantity
x CO
2
-equivalent R410A
= CO
2
-equivalent total
4.78 kg x 2088 kg/kg =
9980 kg
Ä
i.e. there is no testing obligation
Calculation for vamp
air
K 12 and K 15
Refrigerant quantity
x CO
2
-equivalent R410A
= CO
2
-equivalent total
6.70 kg x 2088 kg/kg =
13989 kg
Ä
i.e. there is an annual testing obligation
16 Messages
Messages that arise are shown in the
eco
manager-
touch
control display, each message is saved in the
message log
.
Abb. 2-48: Information window with message
16.1 Possible messages
The overwhelming majority of occurring operating
faults require remedy by qualified personnel.
For some messages, switching off the heat pump (i.e.
de-energizing by switching off the circuit breaker) can
remedy the fault. You will be notified of this option in
the message window that appears in these mes-
sages (
..."disconnect the heat pump from the power
supply for 2 minutes
)
"
.
Overtemperature reset has triggered
The overtemperature reset (OTR) is a safety device
that prevents overheating of the electric heating ele-
ment (optional accessory). Function: The OTR stops
the heating element at a temperature of ~85°C. After
triggering, the OTR must be reset manually
. If
the overtemperature reset trips, this is indicated on
the control display.