Figure 29: Internal connectors
Creating an Ethernet (LAN) Connection
This communication option enables using an Ethernet connection to connect the inverter to the
monitoring portal through a LAN.
Ethernet cable specifications:
l
Cable type – CAT5/CAT6
l
Maximum distance between the inverter and the router – 100 m/ 330 ft.
NOTE
If using a cable longer than 10 m / 33 ft in areas where there is a risk of
induced voltage surges by lightning, it is recommend to use external surge
protection devices. For details refer to:
http://www.solaredge.com/files/pdfs/lightning_surge_protection.pdf.
If
grounded metal conduit are used for routing the communication wires,
there is no need for a lightning protection device.
Figure 30: Example of Ethernet connection