7. Insert the two supplied screws through the outer heat sink fins on both sides of the
inverter and into the bracket (see
Tighten the screws with a torque of 4.0 N*m / 2.9 lb.*ft.
Figure 8: Inserting the bracket screws
8. Fasten the inverter to the surface using the bottom bracket.
Figure 9: Bottom bracket
9. Remove the inverter cover: Open the inverter cover’s ten Allen screws and carefully
pull the cover horizontally before lowering it.
Selecting a Residual Current Device (RCD)
IMPORTANT SAFETY FEATURE
All SolarEdge inverters incorporate a certified internal Residual Current Device
(RCD) in order to protect against possible electrocution and fire hazard in case
of a malfunction in the PV array, cables or inverter. There are two trip
thresholds for the RCD as required for certification (DIN VDE 0126-1-1). The
default value for electrocution protection is 30 mA, and for slow rising current
is 300 mA.