Select
Meter 1
. Verify that the meter at address 1 is
configured as a production meter.
Select
Device Type
è
Revenue Meter
Select
Protocol
è
SolarEdge
Select
Device ID
è
1
Set the CT rating to the value that appears on the
CT: CT
Rating
è
<
xxxxA
>. If the displayed rating is
0 or you cannot change the value, there is no
communication with the meter. Check that the AC
power to the meter is on.
Select
Meter Func.
è
Inverter Production.
Set
Topology
to
Wye or Delta
, in accordance with
the grid and meter type requirements.
Select
Meter 2
and configure its settings:
Select
Device Type
è
Revenue Meter
Select
Protocol
è
SolarEdge
Set
Device ID
è
2
Set the CT rating to the value that appears on the
CT: CT
Rating
è
<
xxxxA
>. If the displayed rating is
0 or you cannot change the value, there is no
communication with the meter. Check that the AC
power to the meter is on.
Revenue Grade Energy Meter with Modbus Connection Installation Guide MAN-01-00609-1.0
Appendix B: Installing Two Meters
61