Meter Function
è
Inverter Production
Protocol
è
SolarEdge
Device ID
è
1
3. Select
Meter 2
to configure the export/import meter in the
following steps:
4. Select
Meter Function
, and choose
Import
from the
following options:
Import
: The meter is installed at the grid
connection point and reads pulses from both
directions - export and import energy.
Consumption
: The meter is installed at the load
consumption point and reads the energy consumed by
the site.
Site Production:
The meter is installed at the inverter
output and reads the energy produced by the inverters
at the site.
Ext. Production
: The meter is used for export limitation
with 3rd party generators and for AC coupling with
non-SolarEdge inverters.
5. Select
Meter Protocol
, and select
SolarEdge
.
6. Set
Device ID
to the address 2 (the address should
correspond to the DIP switch settings).
Revenue Grade Energy Meter with Modbus Connection Installation Guide MAN-01-00609-1.0
58
Configuring the Dual-Meter Connection