Appendix B: Installing Two Meters
You can connect up to two meters on the same bus.
To connect two meters, install two wires into each screw
terminal by twisting the wires together, inserting them into
terminal, and securely tightening. RS485 wiring is daisy-
chained between meters, as described in the following figure:
Figure 16: RS485 chain of meters
Connecting Two Meters
1. Connect the twisted pair wiring to the meters as shown in
2. Wire the RS485 connections between the meters and the
inverter or Commercial Gateway.
3. Set the meters' 120 ohm termination DIP switches as
Revenue Grade Energy Meter with Modbus Connection Installation Guide MAN-01-00609-1.0
Appendix B: Installing Two Meters
55