4. Select
Revenue Meter
è
Meter Func.
è
Import
/
Export
/
Import
/
Consumption / Site Production / Inv.
Production
.
Number of devices is not displayed
If
<-->
is displayed under the ## column in the
Communication status screen, the meter is not communicating
with the inverter. Check the following:
The meter's ID DIP switch settings. Refer to "DIP Switches"
The meter's Termination DIP switch settings. Refer to
"Termination DIP Switches" on page 18.
That the meter is configured as required in the chapter
The RS485 wiring between the meter and the
inverter/Commercial Gateway as specified in
To connect
the meter to the inverter or CCG: on page 24
There are no loose connections at the inverter connectors
and at the meter, specifically the RS485 wiring.
Revenue Grade Energy Meter with Modbus Connection Installation Guide MAN-01-00609-1.0
Appendix A: Troubleshooting the Meter
51