D e v i c e T y p e < M T R >
P r o t o c o l < S E >
D e v i c e I D < 1 >
C T R a t i n g < 2 0 0 >
M e t e r F u n c . < E + I >
T o p o l o g y < W y e >
P T S c a l i n g < 1 >
4. Configure the meter parameters as follows:
Select
Protocol
è
SE
.
Select
Device ID
and enter the Modbus address
corresponding to the ID DIP switch settings on the
meter.
Select
CT Rating
and set the rating to the value that
appears on the CT. If the displayed rating is 0 or you
cannot change the value, it means that there is no
communication with the meter. Check that the AC
power to the meter is on.
Revenue Grade Energy Meter with Modbus Connection Installation Guide MAN-01-00609-1.0
36
Device Configuration