64
L10US-IB20, L10US-IB40, L10US-IB60 L10US-IB00, L15US-IB40,
L15US-IB60 L15US-IB00, L20US-IB60, L20US-IB00 UPS
12.3.
Backfeed installation with relay:
1. Connect the UPS backfeed dry contact to a terminal of the relay R coil. Route the cable
with the other signal cables.
2. Connect the fuse F, the auxiliary contact of relay R, and the coil of C as shown in the
illustration below.
3. Connect C (L1, L2 , L3) with UPS bypass input (L1, L2, L3) as shown in the illustration below.
4. Connect bypass input (N) with mains feeding (N) in the distribution switchgear.
Figure 41 Backfeed diagram