UPS for 400 Vac Grid, Installation Guide, doc. rel. 3.0
53
The Self-loading/PQ mode screen appears:
Figure 35: Enable Self-loading/PQ mode
2.
Select
Enable
and then select
Confirm
.
3.
PQ Mode is enabled.
4.
Transfer system from VF mode to PQ mode with 2 kW active load
(System Menu >
Operation > Self-loading/PQ mode
)
The Self-loading/PQ mode Setup screen appears:
Figure 36: Self-loading/PQ mode setup
5.
Wait until system starts Self-loading/PQ mode.
6.
Navigate to
System Menu > Status
.