NOTE
Only the first and last SolarEdge devices in the chain should be
terminated. The other devices in the chain should have the termination
switch OFF.
To configure the RS485 communication bus with SolarEdge inverters:
By default, all SolarEdge devices are pre-configured as slaves on the RS485-1 port.
Slaves can be further configured using the
RS485-X Conf
option in the
Communication menu.
One device must be set as the master on the RS485 bus. Any SolarEdge device may be
the master (Firefighter Gateway, inverter). If you connect the installation to the
SolarEdge monitoring platform, the device used to connect to the server must be the
master.
The following describes how to configure the master device.
1. Press the
Enter
button until the following message is displayed:
P l e a s e e n t e r
P a s s w o r d
* * * * * * * *
2. Use the three-right most LCD buttons to type in the following password:
12312312
The following menu is displayed:
L a n g u a g e < E n g >
C o m m u n i c a t i o n
R e m o t e S h u t d o w n
P o w e r C o n t r o l
D i s p l a y
M a i n t e n a n c e
I n f o r m a t i o n
3. Short-press the arrow buttons to scroll to the Communication menu. Press the Enter
button to select it.
4. Select
Server
è
RS485-X
Conf (X=1 or 2 depending on the specific physical port
connection) to communicate with different external devices.
5. To configure the master, select the following in the LCD menus:
Communication
è
RS485-1 Conf
è
Device Type
è
SolarEdge
RS485-1 Conf
è
Protocol
è
Master
RS485-1 Conf
è
Slave Detect