Chapter 5: Connecting the Inverter
This chapter explains how to connect the inverter to:
AC grid
DC input
Installing Conduits
Before connecting the inverter, install all conduits as shown below.
Figure 10: Conduit installation
To install a conduit:
1. Switch the DC Safety Switch to OFF.
2. Release the four Allen screws of the Connection Unit cover and remove the cover.
CAUTION!
When removing the cover, make sure not to damage internal
components. SolarEdge will not be held responsible for any components
damaged as a result of incautious cover removal.
3. Install a conduit of the required diameter:
To install a 32 mm conduit, remove the conduit plug together with the reducing
washer.
To install a 25 mm conduit, use the supplied reducing washer.
To install a smaller conduit, use a reducing washer of an appropriate size (not
supplied)
4. If required, ground the conduit by connecting it to the grounding bar, as shown
above.