SolarEdge BI-EU3P Quick Installation Manual Download Page 2

Comm

Enable

LED Indications

Manually Switching to Grid-Connected Mode

In case the grid is back to operation, but, for 

some reason, the "Backup Interface" LED shows 

that backup is ON, you can manually connect 

the grid back to the loads by following the 

below procedure.
When the system is manually switched to the 

grid-connected mode, no backup of the loads is 

possible.
To switch to the grid-connected mode:
1.

Remove the Backup Interface front cover 

as shown above.

2.

Press “Bypass On” on Manual Control 

panel.

3.

Close the external cover.

4 N*m

4

Closing the Backup 

Interface

1.

Using M4 Allen key, secure Backup Interface internal lower cover 

with two screws.

2.

Using M5 Allen key, secure Backup Interface external front cover 

with six screws.

3.

Now you can turn on the main CB and the inverter.

Configuring Installation

1.

Run SetApp.

2.

Scan the QR code on the inverter.

3.

Follow the on-screen instructions.

4.

Configure the import/export meter on SetApp.

SetApp

5

Power Control

Energy Manager

Backup

Configuration

Backup

Commissioning

4 N*m

Grid

Backup

ON

On grid or boot

OFF

Backup mode

Blinking

Firmware upgrade

Fast blinking

Backup interface

received request

to identify itself

All LEDs OFF

No power

ON

Fault or boot 

OFF

No faults

Blinking

Firmware upgrade

Fault

6

Backup system checkup

Note: Before you start, make sure you have the Inverter system operating and producing with battery at above 20%.
Checking the backup operation may cause 2-3 seconds of electricity supply failure to the loads before they are powered up again; if 

you have a load sensitive to such interruption, please disconnect it from the load backup section. 
Make sure the loads are evenly distributed between phases and do not exceed your inverter rating per phase. 

1.

Make sure you have power from the grid and your inverter is working.

2.

Before you start, check that the Battery SoC level is above 20%.

3.

Make sure the Grid LED is ON and there is no fault detected. Turn OFF the main CB coming from the grid. Immediately after 

that, all home loads should shut down and the "On grid" LED should turn OFF.

4.

Wait for a few seconds till all the home loads are powered up again, the LED marked as "Backup" should turn ON.

5.

After a few minutes of stable operation, turn ON the main CB again.

6.

“Backup” LED should turn OFF and the "On grid" LED should turn on again. 

Connecting the Backup Interface

DANGER! 

Before opening the covers and connecting the grid, please make sure that the main CB and the Inverters are OFF.

Note: If your local regulations require a short between Neutral and Protective earth (e. g. according to TNC), use the upper-right 

terminal for the Load Neutral (see the figure below and the Main Connection Scheme).

1.

Strip 100mm around the external grid cable and strip 8mm from the internal wire insulation. If needed, crimp the wire 

ferrules. Open the left gland marked with “Grid” and insert the grid cable. 

Connect the ground wire first. Torque 

6nm. 

Connect the wires Ground (yellow) L1 (brown) ,L2 (black), L3 (gray), and Neutral (blue) to their respective terminals.

2.

Strip 100mm around the external load cable and strip 8mm from the internal wire insulation. If needed, crimp the wire 

ferrules. Open the right gland marked with “Load” and insert the load cable. 

Connect the ground wire first. Torque 

6nm. 

Connect the wires Ground (yellow) ,L1 (brown) ,L2 (black), L3 (gray), and Neutral (blue) and to their respective terminals.

3.

If  your system doesn’t use solaredge home network, connect the Backup Interface to your inverter using a CAT5 E or a 

CAT6. Open the communication gland and insert the communication cable, close the gland.  Pull out the communication 

connector and connect the communication cable wires to the G, A, B, and 12V +/- respectively. Please use a twisted pair 

connection for A and B. Connect the other side of this cable to the inverter. 

4.

Backup Interface includes a built-in meter. If you are using full house backup, you will have to disconnect any other 

external export/import meter and remove it from SetApp. The internal meter must be configured as import/export. If you 

are using partial home backup, you will have to connect and define an external meter on the main panel and define it as 

the import/export meter of the system.

For the Home Hub inverter

installation guide, scan 

Cable

Outer diameter of 25-32mm

Cable cross section of 6

2

-16

2

mm

3

6 N*m

6 N*m

ON

WARNING

!

Only a certified installer is permitted 

to perform this operation 

ON

In backup or boot

OFF

On grid

Blinking

Firmware upgrade

Fast blinking

Backup interface

received request

to identify itself

ON

Connected to the network/ 

received modbus packet/ boot

Blinking

There is no communication 

over RF or RS485

On RF 

not connected 

or temporarily 

disconnected

On RS485 

no packet 

received for 30 seconds

Flickering

Bootloader is upgrading 

software

Fast blinking

Device received request to 

identify itself

Neutral: 

Short with 

the Ground 

(TNC)

1

2

1

2

3

1

2

3

Regular 

Neutral

3

Reviews: