SS4037-02 INSTALLATION MANUAL v1.2

 

 

 

 

Troubleshooting Warnings / Errors 

 

Error 
Code 

Cause 

Solution 

Warnings ( Figure 8) 

1-2 

1.

Inverter / rectifier settings may not be correct. 

2.

Battery cells may be disbalanced  

1.

Check the battery settings 

2.

Contact Solar MD support 

3-4 

System design is not correct. 

Add additional battery, decrease charging / 
discharging current from  
your inverter / rectifier / load 

5-6 

Manual override 

Manual override has been activated - please 
check with your installer 

29-30 

The BMS is ready to switch on after deep discharge / charge 

Connect charger / load to the Battery 

Errors (Figure 9 & 10) 

5,6,7 

The battery is not installed in upright position 

Install the battery in the right position 

15,16,17 

The BMS has been shut down manually or remotely 

Switch on the BMS 

18,19 

The absolute maximum charge/discharge current has been 
achieved 

The BMS will restart automatically, please 
contact support team or approved installer 

21 

The BMS is set for different number cells in series as the actually 
installed 

Contact your installer or Solar MD support team 

22 

Battery cell voltage way too low. 

Fill in the failure report and send to 

[email protected]

 

The unit needs to return to the factory for testing 

23 

Battery cell voltage way too high 

The BMS will restart automatically after pending 
awake condition 

24,25,26,
27,28,30,
31 

BMS internal failure. 

Fill in the failure report and send to 

[email protected]

 

The BMS will be dispatched to you for 
replacement 

29 

Battery factory failure 

Fill in the failure report and send to 

[email protected]

 

The unit needs to return to the factory for testing 

CANBUS Warning (Figure 12) 

1.

Canbus line open. 

2.

Single CANBUS resistor not terminated. 

1.Check if the minimum of two nodes are 
connected on the line with the same 
transmission speed.  
2.Check if  single resistor is terminated via the 
jumper. Located top right of CAN LEDs (Fig 12). 

 

18 

Summary of Contents for SS4037-02

Page 1: ...Solar MD PTY ltd Unit 23 Alternator Park Montague Gardens 7441 Cape Town South Africa INSTALLATION MANUAL SS4037 02 Advanced Lithium Ion battery...

Page 2: ...Inaccuracies 2 Copyrights 3 Safety Information 3 Warnings Cautions 3 Specification 4 Mechanical installation 5 Installing bottom cover plate 6 Electrical installation 7 Commissioning 9 Multicolor mult...

Page 3: ...s available in one standard size and can be paralleled to meet most residential applications The rated voltage is 51 2V nominal to suit 48V systems Larger systems are provided by Solar MD based on spe...

Page 4: ...ghts All information in this document is subject to the copyright of Solar MD Pty Ltd Additional information is available upon request Safety Information This manual contains important instructions an...

Page 5: ...v ov oc Position x y x Acceleration x y z Temperature ot ut Nominal voltage 51 2V Protection phy Mechanical relay NO Number of battery modules 1 module Com CANBUS isolation Yes 1 5kV Weight 37kg Trans...

Page 6: ...2181 SS4037 02 INSTALLATION MANUAL v1 2 Mechanical installation Figure 1 Rear Battery Bracket Please use the correct mounting screws for the correct wall surface Screw head should not be bigger than 1...

Page 7: ...037 02 INSTALLATION MANUAL v1 2 Figure 2 Maximum tilt angle Installing bottom cover plate Figure 3 Bottom cover installation for single or dual cable exit points The Battery comes with two covers for...

Page 8: ...Solar MD PTY ltd E info solarmd co za T 021 555 2181 SS4037 02 INSTALLATION MANUAL v1 2 Electrical installation Step 1 Before connecting anything be sure that battery is off and the ON OFF switch fig4...

Page 9: ...ttery terminal must be with the correct size cable Based on the rated current of the battery and inverter as well as cable length Figure 5 connection terminal Step 2 Connect the negative cable to the...

Page 10: ...ge can cause very high equalization current which can burn the fuses of the battery Caution Measure the voltage of the battery before connecting the dc Cables Step 3 Turn BMS board ON OFF switch to th...

Page 11: ...utton again within 3 seconds The predefined functions are 1 Reserved 2 Change indication LED function between Show Capacity Show Current and Off 3 Reserved 4 Wake up if Sleep mode is active 5 Activate...

Page 12: ...to GREEN at 100 state of charge The flashing code for charge goes through illumination interruption for 1 interval and slow illumination into the color based on the SoC for 5 intervals The flashing c...

Page 13: ...isplaying warnings and Errors If an Error is present the ERROR LED fig 7 top right will start blinking synchronized with the LEDs at Indication led group fig 7 bottom If Warning is present the WARN LE...

Page 14: ...Battery discharging current is higher than the maximum allowed electrical discharging current 4 Override ON active protection is forced to work at extreme levels for preset period 5 Override OFF activ...

Page 15: ...Protection in critical stage pending shutdown in 3sec 12 Battery Protection in critical stage Override mode reached the maximum permitted values pending shutdown in 3sec 13 Battery Protection in criti...

Page 16: ...Red Stat LED ERROR Cell voltage too high 23 Internal error Additional information on request 24 Internal error Additional information on request 25 Internal error Additional information on request 26...

Page 17: ...ATION MANUAL v1 2 CANBUS connection Bms EM used CAN 2 0B 500000 kb Connecting other device operating at different speed rate is not allowed For connection please use twisted pair wires in a shielded c...

Page 18: ...ing for canbus only Reading this warning is possible with pulse counting CANBUS line open or no termination resistor set 1 CAN BUS line in initialization stage Canbus init occur when the line was open...

Page 19: ...The absolute maximum charge discharge current has been achieved The BMS will restart automatically please contact support team or approved installer 21 The BMS is set for different number cells in ser...

Page 20: ...rge 48V Check that the Equalisation function are disalled then verify if there is a voltage difference on the inverter display and the battery terminals 0 3C discharge charge current If so adjust the...

Reviews: