Quick Start Guide
Electronic A.C. current meter for DIN rail mounting with MID
declaration of conformity and ModBus interface
(converter connection meter)
Warning
The meter's case is sealed and may not be opened. Opening the meter and/or breaking the seal invali-
dates the warranty. Please make sure that all of the cables are mounted free from mechanical stress.
Only meters with the MID declaration of conformity can be used for tariff applications.
Important note on adjusting the converter ratio.
The converter ratio can only be set once with this meter.
When the meter is connected to power, the display alternates between “Set CT” and “CT5 0005.” If one of the arrow
keys is pressed, the fi rst number from the left blinks. Defi ne the secondary power between /1A and /5A and con-
fi rm the selection by pressing both of the arrow keys at the same time for 3 seconds. After that, defi ne the primary
current by selecting the 4 numbers from left to right with the keys as described above. Confi rm every number by
pressing both arrow keys for 3 seconds.
The primary power can be freely defi ned in steps of 5A from 0005 to 9995. Once the last digit has been confi rmed,
the converter ratio is saved and cannot be changed again.
Please note
This document is only a quick start guide and does not cover all of the device's functions. Detailed specifi cations
and descriptions are available at
www.kdk-dornscheidt.de
.
Information for your safety
This quick start guide does not contain all of the safety instructions for operating the meter. Due to special operat-
ing conditions and/or local laws and regulations, additional measures may be required.
Trained Personnel
The meter may only be installed and connected by a trained, qualifi ed specialist. Trained, qualifi ed specialists are
those who are certifi ed to put devices, systems and circuits into operation, to switch them on, to ground them and
to mark them according to safety standards and regulations.
The following values are displayed successively in the automatically rotating display:
Energy fl ow direction display per phase 1 2 3
R = Reverse, F = Forward
Active energy (forward) in kWh (OBIS: 1.8.0)
Accumulating
Active energy (reverse) in kWh (OBIS: 2.8.0)
Accumulating
Active power (total)
For a complete overview of all of the display values available in the manual mode, please refer to the technical
descriptions in the download section at
www.kdk-dornscheidt.de
. (German).
Changing the Modbus address with the sensor buttons on the meter
The Modbus address can be changed from the Program Menu (see supplementary sheet) under “PRO – 2.” Addi-
tional changes are possible. A password is required to access the sub-menu “PRO – 3.” The default password is
“0000” – it can be changed via the programming.
Example of the MID label
The declaration of conformity and certifi cation
(EN 50470) you will fi nd current on:
www.
kdk-dornscheidt.de
For questions about the Solar-Log™ or on how
to confi gure the meter in the Solar-Log™, please
contact our support team:
or: +49 7428 94 18 660
For questions about the meter, please contact the
manufacturer:
or: +49 2244 919940
M 15
0122
Solare Datensysteme GmbH • www.solar-log.com • Subject to change without notice. | EN | 03.2020 | Version 1.7
V1.1
Technische
Daten:
Nennspannung
:
230/
400V
AC
Strom:
0,25
‐
5(100)A
Frequenz:
50Hz
Messgröße:
Wirkverbrauch,
Rücklaufsperre
Genauigkeitsklasse:
B
Eigenverbrauch:
<10VA
‐
<2W
Breite:
4TE
(70mm)
Impulsausgang
LED:
10.000
Imp/kWh,
2,5ms
S0–
Impulsausgang:
1.000
Imp/kWh,
25ms
Arbeitstemperatur:
‐
25°C
bis
+55°C
Max.
rel.
Lu
�
feuchte:
75%
im
Mi
�
el,
kurzzei
�
g
95%
Registrierte
Harmonische:
0,05–
0,25kHz
LED:
rot
blinkend:
Bezug
>
4W,
Impulsrate
=
Verbrauch
Display:
6+2
Digits
(999999,11
kWh)
Maximaler
Leiterquerschni
�
:
Hauptklemmen:
max.
35mm²
Zusatzklemmen:
max.
2,5mm²
Baudrate
ModBus:
9600baud
Anschlussschema:
Zählertyp:
PRO380,
100A
Nach
Schaltungstyp
1000
(DIN
43856)
Input
„L1,
L2,
L3“
Zuleitungseingang
Phase
L1,
L2,
L3
Output
„L1,
L2,
L3“
Zuleitungsabgang
Phase
L1,
L2,
L3
Klemme
„N“
Neutralleiteranschluss
N
Klemmen
18,
19
S0
‐
Impulsausgang
„Bezug“
(Kl.
18=
„+“)
Klemmen
20,
21
S0
‐
Impulsausgang
„Lieferung“
(Kl.
20=
„+“)
Klemme
22,
23
ModBus–
Anschluss
Klemme
22
‐
>A,
23
‐
>B
Klemme
24,
25
externe
Tarifumschaltung
(230V
AC)
Klemmleistenstecker
Solar
Log
PRO380
Klemme
Klemme
1
‐
>
22
(A)
4
‐
>
23
(B)
V1.1
Alle
Anzeigewerte
des
Zählers:
Durch
Drücken
der
Tasten
wechselt
der
Zähler
von
der
automa
�
sch
rollierenden
Anzeige
in
die
manuelle
Anzeige.
Hier
können
mi
�
els
Tastendruck
alle
verfügbaren
Anzeigewerte
der
Reihe
nach
aufgerufen
werden.
Wird
keine
gedrückt,
kehrt
der
Zähler
nach
kurzer
Zeit
wieder
in
den
automa
�
schen
Modus
zurück.
In
der
automa
�
sch
rollierenden
Anzeige
werden
nacheinander
die
folgenden
Werte
angezeigt:
Für
eine
vollständige
Übersicht
aller
verfügbaren
Anzeigewerte
im
manuellen
Modus
beachten
Sie
bi
�
e
die
ausführliche
technische
Beschreibung
als
Down
‐
load
auf
www.kdk
‐
dornscheidt.de.
Änderung
der
Modbus
Adresse
mit
Hilfe
der
Sensortasten
am
Zähler
:
1.
Mit
der
linken
Pfeiltaste
durch
das
Menü
blä
�
ern,
bis
„addr
001“
angezeigt
wird
2.
Zur
Änderung
der
Adresse
beide
Pfeiltasten
für
5
sec
drücken
–
Anzeige
blinkt
1x
auf,
wenn
Änderungsmodus
ak
�
v
ist.
3.
Mit
der
rechten
Pfeiltaste
Adresswert
erhöhen,
bis
gewünschte
Adresse
angezeigt
wird
4.
Zum
Verlassen
des
Änderungsmodus
nochmals
beide
Pfeiltasten
für
5
sec
drücken
5.
Verlassen
des
Änderungsmodus
wird
durch
blinken
des
Displays
bestä
�
gt
6.
Sollte
diese
Bestä
�
gung
nicht
erfolgen
ist
Gerät
immer
noch
im
Ände
‐
rungsmodus
–
Bestä
�
gung
nochmals
versuchen
7.
Kontrolle
der
eingestellten
Adresse
durch
annavigieren
wie
1)
Energierichtungsanzeige
pro
Phase
1
2
3
r
=
Lieferung
(Reverse)
F
=
Bezug
(Forward)
Wirkenergie
Bezug
in
KWh
(OBIS:
1.8.0)
Saldierend
Wirkenergie
Lieferung
in
KWh
(OBIS:
2.8.0)
Saldierend
Momentan
‐
Leistung
(Gesamt)