18
Remote Shutdown Via the DB-9 Connector
The S2K unit can be shut down remotely by shorting Pins 5 and 6 or
via Pins 4 and 5 of the DB-9 connector.
Shutdown Via Pins 5 & 6
When Pin 6 is shorted to Pin 5, the UPS output is shut off regardless
of what mode the UPS is operating in. The UPS cannot be started as
long as the pins are shorted. When the short is removed, the UPS out-
put can be enabled by pressing the ON/OFF/Alarm Silence button.
Shutdown Via Pins 4 & 5
While the UPS is operating on battery (with no battery test in
progress), a 5-12VDC signal for 2 seconds or longer is required to sig-
nal a shutdown. Signals for less than 2 seconds are ignored.
After Pin 4 receives the shutdown signal, a 2-minute shutdown timer
inside the UPS begins a countdown. The timer cannot be stopped. If
mains power returns during the 2-minute timer countdown, the shut-
down timer continues until the end of 2 minutes and then the UPS
turns off.
By default, autorestart is enabled so the UPS will restart after
10 seconds. If autorestart is disabled via MultiLink software, the UPS
remains off until a manual restart.
USB Interface Port
The S2K unit has a USB interface port for communication that will
work with most power management software and provide UPS sta-
tus and management of the automatic orderly shutdown of the com-
puter. The S2K’s USB communications meets HID standard,
version 1.11
Data Line Protection Connectors
Data line (IN & OUT) connectors are located on the rear of the UPS
and provide transient voltage surge suppression (TVSS) for Phone/
Fax/DSL/Internet/Modem devices.