Chapter 2 - About FG-200 HSE/FF Modbus
Version EN-112021-1.30.3
9
2
About FG-200 HSE/FF Modbus
The Softing FG-200 HSE/FF Modbus is a gateway connecting Modbus TCP or FOUNDATION fieldbus High
Speed Ethernet (HSE) to FOUNDATION fieldbus H1 field devices. It provides fast access to process data,
while making use of FOUNDATION Fieldbus advantages such as reduced cabling, central field device
parametrization, comprehensive diagnostics or intrinsically safe device segments. For simple installation it
is compatible with the R. STAHL bus-Carrier Series 9419 and Fieldbus power supplies Series 9412.
2.1
Intended use
The FG-200 can be used for integrating up to four FF H1 links into a Modbus control system or for
communication between FF H1 devices and FF HSE network. The gateway can be operated in both
hazardous and non-hazardous areas. Any other use is not intended. Follow the instructions in this guide on
how to use the FG-200.
2.2
Specifications
Power supply
18 VDC...32 VDC; SELV/PELV supply mandatory
Typical input current is 200 mA; maximum is 1 A (considering the rush-in
current at switch-on).
FF-H1
Four FF-H1 channels, compliant with type 114 of the FF physical layer profile.
The Fieldbus voltage range is from 9 VDC...32 VDC. Preferred value is 24 VDC.
Ethernet
IEEE 802.3 100BASE-TX/10BASE-T
Minimum ambient
operating temperature
-40 °C (see
for the maximum ambient temperature
depending on the mounting position)
Storage temperature
-40 °C...+85 °C
Relative humidity
10 %...95 % (non-condensing)
Altitude
Must not exceed 2,000 m
Location
Indoor use only; no direct sunlight
Coating
Conformal Coating based on ANSI/ISA-S71.04 G3
Safety standard
IEC/EN/UL 61010-1 Safety requirements for electrical equipment for
measurement, control and laboratory use - Part 1: General requirements
IEC/EN/UL 61010-2-201 Safety requirements for electrical equipment for
measurement, control and laboratory use - Part 2-201: Particular
requirements for control equipment (both with CB scheme).
Ingress protection
IP20
2.3
System requirements
§
24V power supply
§
power conditioner
§
PC with operating system Windows 7 or Windows 8.1 (both 32 bit or 64 bit supported)
§
Web browser (Microsoft Internet Explorer version 8.0 or higher, Mozilla Firefox version version 35 or
higher)
17
Summary of Contents for FG-200 HSE/FF
Page 1: ...Softing Industrial Automation GmbH FG 200 HSE FF Modbus User Manual Version EN 112021 1 30 3...
Page 49: ...Chapter 6 Using the web interface Version EN 112021 1 30 3 49...
Page 56: ...FG 200 HSE FF Modbus User Manual 56 Version EN 112021 1 30 3...
Page 77: ...Chapter 10 ATEX Type Examination Certificate Version EN 112021 1 30 3 77...
Page 78: ...FG 200 HSE FF Modbus User Manual 78 Version EN 112021 1 30 3...
Page 81: ...Chapter 12 Declarations of conformity Version EN 112021 1 30 3 81...