Chapter 3 - Installation
Version EN-112021-1.30.3
23
3.1.10 Powering up the device
Turn on the power supply. The boot process takes a few seconds. For indication of proper operation of a
.
3.1.11 Adding a second FG-200 to form a redundant set of FG-200
For adding a second FG-200 to an already commissioned FG-200 that is operating in the role "Primary, no
backup", the following steps are required:
1. Set the IP configuration (IP address and subnet mask) of the second FG-200 using the same IP subnet
as the primary device (see
).
2. Connect the H1 links to the terminal blocks of the H1 interfaces. Make sure to connect each H1 link to
the same channel (CH 1 .. CH 4) on both FG-200s.
3. Connect the second FG-200 to the Ethernet switch or hub.
4. Connect both RDL interfaces as mentioned in Section
5. Connect the second FG-200 to a 24 V DC power supply. Use different or redundant power supplies for
redundant FG-200s.
6. After turning on the power supply the boot process takes approx. 50 seconds.
7. The second FG-200 will take over the configuration data from the primary device and will start
operation in the role "secondary". For more details about proper operation as a secondary device see
.
Hint
Refer to Section
for more information on the redundancy concept.
57
25
21
57
21
Summary of Contents for FG-200 HSE/FF
Page 1: ...Softing Industrial Automation GmbH FG 200 HSE FF Modbus User Manual Version EN 112021 1 30 3...
Page 49: ...Chapter 6 Using the web interface Version EN 112021 1 30 3 49...
Page 56: ...FG 200 HSE FF Modbus User Manual 56 Version EN 112021 1 30 3...
Page 77: ...Chapter 10 ATEX Type Examination Certificate Version EN 112021 1 30 3 77...
Page 78: ...FG 200 HSE FF Modbus User Manual 78 Version EN 112021 1 30 3...
Page 81: ...Chapter 12 Declarations of conformity Version EN 112021 1 30 3 81...