Table 7-1 Eventlist
Code
Name
Description
Solution
ID001
GridOVP
The grid voltage is too
high
If the alarm occurs occasionally, the
possible cause is that the electric grid is
abnormal
occasionally.
Inverter
will
automatically return to normal operating
status when the electric grid’s back to
normal.
If the alarm occurs frequently, check
whether the grid voltage/frequency is within
the acceptable range. If yes, please check
the AC circuit breaker and AC wiring of the
inverter.
If the grid voltage/frequency is NOT within
the acceptable range and AC wiring is
correct, but the alarm occurs repeatedly,
contact technical support to change the grid
over-voltage,
under-voltage,
over-frequency, under-frequency protection
points after obtaining approval from the
local electrical grid operator.
ID002
GridUVP
The grid voltage is too
low
ID003
GridOFP
The grid frequency is
too high
ID004
GridUFP
The grid frequency is
too low
ID005
GFCI
Charge Leakage Fault
Internal faults of inverter, switch OFF
inverter, wait for 5 minutes, then switch ON
inverter. Check whether the problem is
solved.
If no, please contact technical support.
ID006
OVRT fault
OVRT
function
is
faulty
ID007
LVRT fault
LVRT function is faulty
ID008
IslandFault
Island protection error
ID009
GridOVPInstant1
Transient overvoltage
of grid voltage 1
ID010
GridOVPInstant2
Transient overvoltage
of grid voltage 2
ID011
VGridLineFault
Power grid line voltage
error
ID012
InvOVP
Inverter
voltage
overvoltage
ID017
HwADFaultIGrid
Power
grid
current
sampling error
ID018
HwADFaultDCI
Wrong sampling of dc
component
of
grid
current
ID019
HwADFaultVGri
d(DC)
Power grid voltage
sampling error (DC)
ID020
HwADFaultVGri
d(AC)
Power grid voltage
sampling error (AC)
ID021
GFCIDeviceFault
(DC)
Leakage
current
sampling error (DC)
ID022
GFCIDeviceFault
(AC)
Leakage
current
sampling error (AC)
ID023
HwADFaultDCV
Error in dc component
sampling
of
load
voltage
ID024
HwADFaultIdc
Dc
input
current
sampling error