7.1 Trouble shooting
This section contains information and procedures for solving possible problems with the sofar
30~40KTL inverter.
In case of problem with inverter, check the following tips.
Check the warning fault messages or Fault codes on the inverter information panel. Record
it before doing anything further.
EventList information
solution
EventList Name
EventList NO.
GridOVP
ID01
GridUVP
ID02
GridOFP
ID03
GridUFP
ID04
Trouble shooting and maintenance
7
Outlines of this chapter
This topic describes how to perform daily maintenance and troubleshooting to ensure long-
term proper operation of the sofar 30~40KTL inverter.
If inverter does not display any Fault, please check the following lists.
- Is the inverter located in a clean, dry, adequately ventilated place?
- Is the DC switch turned ON?
- Are the cables adequately sized and short enough?
- Are the input and output connections and wiring in good condition?
- Are the configuration settings correct for the particular installation?
- Are the display panel and the communications cable properly connected and undamaged?
Follow the steps below to view recorded problems:
Press “ESC” to enter the main menu in the normal interface. In the interface screen select
“Event List”, then press “OK” to enter events.
Table 7-1 Eventlist
HwAcOCP
AcRmsOCP
HwADFaultIGrid
PVUVP
Vlvrtlow
Reserved
PvOVP
IpvUnbalance
PvConfigSetWrong
GFCIFault
HwBoostOCP
Check whether too few PV modules are series
connected in a PV string, thus the voltage(Vmp) of the
PV string is lower than the minimum operating
voltage of SOFAR inverter. If yes, adjust the number
of series connected PV modules to increase the
voltage of the PV string to fit the input voltage range
of SOFAR inverter. SOFAR inverter automatically
returns to normal operating status after correct
adjustments.
Check the AC wiring connection to the electric grid, if
it’s correct, please contact SOFAR technical support
.
Reserved
Check whether too many PV modules are series
connected in a PV string, thus the voltage(Voc) of the
PV string is higher than the maximum input voltage of
SOFAR inverter. If yes, adjust the number of series
connected PV modules to decrease the voltage of the
PV string to fit the input voltage range of SOFAR
inverter. SOFAR inverter automatically returns to
normal operating status after correct adjustments.
Check the input mode(parallel mode/ independent
mode) setting of SOFAR inverter according to Section
4.5 of this user manual.
If the fault occurs occasionally, the possible cause is
that the external circuits are abnormal occasionally.
SOFAR inverter automatically returns to normal
operating status after the fault is rectified.
If the fault occurs frequently and lasts a long time,
check whether the insulation resistance between the
PV array and earth(ground) is too low, then check
the insulation conditions of PV cables.
All rights reserved
Shenzhen SOFARSOLAR Co ., Ltd.
C
55
All rights reserved
Shenzhen SOFARSOLAR Co ., Ltd.
C
56
User manual
User manual
Trouble shooting and maintenance
Trouble shooting and maintenance
If the alarm occurs occasionally, the possible cause
is that the electric grid is abnormal occasionally.
SOFAR inverter automatically returns to normal
operating status when the electric grid’s back to
normal.
If the alarm occurs frequently, check whether the
grid voltage/frequency is within the acceptable
range. If no, contact SOFAR technical support. If
yes, check the AC circuit breaker and AC wiring of
the SOFAR inverter.
If the grid voltage/frequency is within the acceptable
range and AC wiring is correct, while the alarm
occurs repeatedly, contact SOFAR technical support
to change the grid over-voltage, under-voltage, over-
frequency, under-frequency protection points after
obtaining approval from the local electrical grid
operator.
HwADFaultDCI
ID24
ID23
ID22
ID21
ID20
ID15
ID16
ID17
ID05
ID06
ID09
ID10
ID11
ID12
ID13
ID14
ID07-ID08
ID18
HwADFaultVGrid
ID19
GFCIDeviceFault
Check whether the input current is higher than the
maximum input current of SOFAR inverters, then
check the input wiring, if both are correct, please
contact SOFAR technical support.
MChip_Fault
HwAuxPowerFault
BusVoltZeroFault
IacRmsUnbalance
ID15-ID24 are internal faults of SOFAR inverter, turn
OFF the “DC switch”, wait for 5 minutes, then turn
ON the “DC switch”. Check whether the fault is
rectified. If no, please contact SOFAR technical
support.
Reserved
Reserved
EventList description
The power grid voltage is
too high
The power grid voltage is
too low
The power grid frequency is
too high
The power grid frequency is
too low
The input voltage is too low
Low voltage across
Reserved
The input voltage is too
high
I n p u t c u r r e n t i s n o t
balanced
Incorrect input mode
GFCI Fault
Phase sequence errors
Ihe input current is too
h i g h , a n d h a s h a p p e n
hardware protection
The grid current is too
h i g h , a n d h a s h a p p e n
hardware protection
The grid current is too high
The grid current sampling
error
The DCI sampling error
The grid voltage sampling
error
The GFCI sampling error
The master chip fault
The auxiliary voltage error
The bus voltage sampling
error
The Output current is not
balanced
Sofar 30K~40KTL
Sofar 30K~40KTL
Document Version 1.0(2015.08.06)
Document Version 1.0(2015.08.06)