PART P MULTIFUNCTION DIGITAL LOOP TESTER
Tests no-trip loop, PFC, socket, mains voltage & polarity
PDL 310
U S E R M A N U A L
0 6 / 0 6
Page 1: ...PART P MULTIFUNCTION DIGITAL LOOP TESTER Tests no trip loop PFC socket mains voltage polarity PDL 310 U S E R M A N U A L 0 6 0 6 ...
Page 2: ...010 1 PDL 310 At Socket See our Engineers constantly look for improvement If there is any aspect of your Socket See tester you would like to comment on please visit our website at www socketandsee co uk or email davidh kewt co uk or Free Fax at 0800 7831385 with any suggestions We promise all communications will be acknowledged We value YOUR opinion Important calibration check box note l Because o...
Page 3: ...remely rare this miswire condition can exist so if your test shows this fault do not proceed if in any doubt advise your customer to contact their supply company immediately overview FUSE100A FUSE100A From Supply Company Live Phase to Meter Neutral to Meter To Main Earthing Terminal Neutral to Meter Live Phase to Meter To Main Earthing Terminal From Supply Company Correct Polarity REVERSE POLARITY...
Page 4: ...y company of the problem If the three socket LED s are GREEN correct and the correct voltage is displayed you can proceed to Polarity Test The reasons for Polarity Test are covered in detail on the previous page of this User Guide To carry out the test apply firm thumb pressure to the Polarity Test Pad note this pad does not depress The three Socket Test LED s should remain GREEN everything is cor...
Page 5: ...isplay display default L N voltage measurement 1 On off button 7 PFC Prospective Fault Current Result 5 6 Test push button loop test reading default Operation a detailed view of the PDL 310 Note numbers also indicate sequence of test 5 overview 4 Polarity test pad ...
Page 6: ...t circuit current selected C HANDSFREE operation D Ohms symbol E Volts AC L N F Fault current G Wait result calculation in progress H Tester has gone over operating temperature I Greater than less than indication J Battery Condition good 6 PDL 310 Overview of the display G C B A D E F H I J ...
Page 7: ...portant test is discussed in full on pages three and four of this manual please read 5 6 The push to test switch must be operated to initiate test except if this button is held down for approx two seconds HANDSFREE testing is selected which is very useful for testing at DB s Distribution Boards luminaires or similar connecting strips Your tester defaults to no trip loop testing when you first swit...
Page 8: ...ange Accuracy 0 00 to 9 99Ω 5 5 digits 10 00 to 99 9Ω 4 4 digits 100 00 to 500Ω 4 4 digits PFC Measurement 10A 9 99kA This is a calculated measurement whose accuracy is derived from the Loop Test result Over Voltage Protection 440V AC No damage complete recovery Power 4 x AA batteries not included Battery life BS EN 61557 10 000 test or shelf life of batteries installed Environmental Operating Tem...
Page 9: ...correctly wired one or more LED s will go to FLASHING RED to indicate there is a a socket miss wire or other fault If flashing red or orange occurs using the touch pad at this stage this should show where the socket wiring problem is as per the example below A unique feature of your tester is the ability to display by the position of the red LED s where the problem is EARTH LIVE Phase or NEUTRAL A...
Page 10: ...10 PDL 310 ...
Page 11: ...strial www socketandsee co uk Unit 4 Century Road High Carr Business Park Newcastle Staffordshire UK ST5 7UG T 44 0 1782 567096 F 44 0 1782 567095 Socket See Limited A division of the Kew Technik Group of companies 11 ...
Page 12: ...E miswire L N E Warble 6 Faulty N L E miswire NC L N Warble 7 Faulty N E miswire NC N L Warble 8 Faulty N NC E L Warble 9 Faulty N L E reverse NC L E Warble 10 Faulty E L N reverse L NC N Warble 11 Faulty E N NC L Warble 12 Faulty E N miswire E NC L Warble 13 Faulty E L N miswire L NC E Warble 14 Faulty L N E miswire L N NC Warble 15 Faulty L E miswire N L NC Warble 16 Faulty L N E miswire E L NC ...