Vega-MV Installation 5.2
5.1.2 MV-EXTPSU3 Backup Power Supply
Ventilation air flow for the MV-EXTPSU3 backup power supply is front-to-back. See Section
11.3 “Ventilation” on page 196.
5.2 Rack Mounting
The 1U Vega-MV frames can be installed in 19” bays.
5.2.1 Before Rack Mounting
Vega-MV frame notes:
•
The Vega-MV1RU frame has a depth of approximately 511mm (20.1 Inches),
including connectors.
•
Exhaust grilles are located on the upper and left side panels at a depth of
approximately 412mm (16.2 Inches) from the front panel.
•
Make sure that sufficient space is available for the 1 RU frame.
•
See Section 5.1 for ventilation details.
5.2.2 Mounting in a Rack
When rack-mounting the frame:
1.
Place the unit on a suitably specified and installed rack shelf.
2.
Secure the unit into the rack using the front ears using the correct rack mount screws
or bolts. (See Figure 35.)
•
Maximum operating ambient temperature must be less than 40°C.
•
The inlet and outlet vents must not be obstructed and should be periodically
cleaned and kept free from the build-up of dust.
•
For ventilation purposes, there must be a gap of at least 50mm (2 inches) for the
front air inlet and rear air outlet grilles.
•
Do not rack-mount the Vega-MV frame using only the front rack ears.
•
If installing equipment immediately above or below the Vega-MV unit it is essential
to ensure that the ventilation outlets are not obstructed. For ventilation details see
section 5.1.
•
For ventilation purposes, there must be a gap of at least 50mm (2 inches) for the
front inlet fans and rear outlet grilles.
•
You must allow at least 100mm (4 inches) of space at the rear of the frame for
cables and connections.