5.6 Installation criteria for UL certification
Integral solid state short circuit protection does not provide branch circuit protection. Branch circuit
protection must be provided in accordance with the Manufacturer Instructions, National Electrical
Code and any additional local codes.
The drive does not provide Motor Overload protection. External or remote Motor Overload protection
shall be provided in the end-use applications.
The drive is intended to be used with motors that must have integral thermal protection.
The integral thermal protection signal shall be connected on the equipment, on terminal "E1, pins
1-2 for models 315X-XX, 325X-XX, 350X-XX.
Signal was rated maximum 5Vdc, 5mA.