2012/10/17 10:39:46 START PROGRAM: 7
Oper: 255
Cycle N.: 288
2012/10/17 10:40:17 START PHASE N.: 1
2012/10/17 10:41:12 Inflow Detergents
P1:0.40%
2012/10/17 10:42:26
TL1: 22.7
TCL: 22.5
2012/10/17 10:42:26 Start heating
Target temp. 93
2012/10/17 10:56:12
TL1: 94.1
TCL: 93.6
2012/10/17 10:57:36
TL1: 93.9
TCL: 93.4
2012/10/17 10:57:52
TL1: 94.1
TCL: 93.6
2012/10/17 10:59:43
TL1: 93.9
TCL: 93.4
2012/10/17 10:59:58
TL1: 94.1
TCL: 93.6
2012/10/17 11:01:53
TL1: 93.9
TCL: 93.4
2012/10/17 11:02:08
TL1: 94.1
TCL: 93.6
2012/10/17 11:04:12
TL1: 93.9
TCL: 93.4
2012/10/17 11:04:26
TL1: 94.1
TCL: 93.5
2012/10/17 11:05:53 Ao>=15983
2012/10/17 11:05:53 Start heating
Target temp. 0
2012/10/17 11:05:53
TL1: 94.1
TCL: 93.6
2012/10/17 11:07:49 START PHASE N.: 2
2012/10/17 11:08:41 Inflow Detergents
P2:0.20%
2012/10/17 11:09:34
TL1: 43.3
TCL: 42.3
2012/10/17 11:09:34 Start heating
Target temp. 0
2012/10/17 11:11:34
TL1: 59.7
TCL: 59.2
2012/10/17 11:11:34 Start heating
Target temp. 0
2012/10/17 11:11:34
TL1: 59.7
TCL: 59.2
2012/10/17 11:12:33 START PHASE N.: 3
2012/10/17 11:13:19 Inflow Detergents
2012/10/17 11:13:41
TL1: 36.9
TCL: 36.5
2012/10/17 11:13:41 Start heating
Target temp. 0
2012/10/17 11:15:41
TL1: 49.9
TCL: 49.5
2012/10/17 11:15:41 Start heating
Target temp. 0
2012/10/17 11:15:41
TL1: 49.9
TCL: 49.5
2012/10/17 11:16:41 START PHASE N.: 4
2012/10/17 11:17:26 Inflow Detergents
2012/10/17 11:17:49
TL1: 33.3
TCL: 32.9
2012/10/17 11:17:49 Start heating
Target temp. 75
2012/10/17 11:25:47
TL1: 76.2
TCL: 75.7
2012/10/17 11:26:30 Start heating
Target temp. 0
2012/10/17 11:26:30
TL1: 76.9
TCL: 76.5
2012/10/17 11:27:29
Start drying: TA_TARGET: 120 TA1: 73
2012/10/17 12:04:47
End drying: TA1: 89
2012/10/17 12:09:07 END PROGRAM: 7
================================================================================
fig. 35 – Example of
cycle data
stored in the
appliance’s memory
.
(The first phase is referred to as “PHASE N.1”
with effect from main firmware version 2.0.0 of 23/09/2013,
it was formerly referred to as “PHASE N.0”)
The double line marks the
start and end of a program
Consecutive number of cycle
P1 detergent dispensing
First phase, called “1”
Phase Target temperature
A0 value reached
Second phase, called “2”
Drying phase, with Target
temperature in Dryer duct
The two tank temperature
probes are called:
TL1 – working probe
TCL – control probe