Installation
17
EN
5 Installation
5.1 Clearances above and around domestic appliances
This appliance must be installed by an
authorised person in accordance with this
instruction manual, AS/NZS 5601.1 –
Gas installations (installation and pipe
sizing), local gas fitting regulations, local
electrical regulations, Building Code of
Australia and any other government
authority.
Requirements
1.
Overhead clearances –
(Measurement A)
Range hoods and
exhaust fans shall be installed in
accordance with the manufacturer’s
instructions. However, in no case shall
the clearance between the highest part
of the hob of the cooking appliance and
a range hood be less than 600 mm or,
for an overhead exhaust fan, 750 mm.
Any other downward facing combustible
surface less than 600 mm above the
highest part of the hob shall be protected
for the full width and depth of the
cooking surface area in accordance
with Clause 5.12.1.2. However, in no
case shall this clearance to any surface
be less than 450 mm.
2.
Side clearances – (Measurements B &
C)
Where B, measured from the
periphery of the nearest burner to any
vertical combustible surface, is less than
200 mm, the surface shall be protected
in accordance with Clause 5.12.1.2 to a
height C of not less than 150 mm above
the hob for the full dimension (width or
depth) of the cooking surface area.
Where the cooking appliance is fitted
with a ‘splashback’, protection of the
rear wall is not required.
Summary of Contents for SRA964NGH
Page 28: ......