16 - INSTALLATION
91477A688/A
spindle (depending on the model) until the
correct minimum flame is achieved.
3. Refit the knob and verify that the burner
flame is stable.
4. Turn the knob rapidly from the maximum to
the minimum setting: The flame should not go
out.
5. Repeat the operation on all the gas taps.
Adjusting the minimum setting for LPG
Tighten the screw located at the side of the cock
spindle clockwise all the way.
Lubricating the gas cocks
Over time the gas cocks may become difficult to
turn and get blocked. Clean them internally and
replace the lubrication grease.
Burner and nozzle characteristics tables
The nozzles not provided are available at Authorised Service Centres.
Electrical connection
General information
Check the mains characteristics against the data
indicated on the plate.
The identification plate bearing the technical
data, serial number and brand name is visibly
positioned on the appliance.
Do not remove this plate for any reason.
The appliance must be connected to ground
using a wire that is at least 20 mm longer than
the other wires.
The appliance can work in the following modes:
• 220-240 V 1N~
fig. 1
Fixed connection
Fit the power line with an all-pole circuit breaker
with a contact separation distance sufficient to
provide complete disconnection in category III
overvoltage conditions, pursuant to installation
regulations.
Following adjustment to a gas other
than the one originally set in the factory,
replace the gas setting label on the
appliance with the one corresponding
to the new gas. The label is inserted
inside the nozzle pack (where present).
Lubrication of the gas cocks should be
performed by a specialised technician.
NG 1.0 kPa
UR2 int.
UR2 ext.
R
AUX
Nominal gas consumption (MJ/h)
3.6
14.4
9.0
3.9
Nozzle diameter (1/100 mm)
81
170
90
140
Reduced flow rate (MJ/h)
1.4
4.3
1.4
2.9
ULPG 2.75 kPa
UR2 int.
UR2 ext.
R
AUX
Nominal gas consumption (MJ/h)
3.2
14
9.0
3.9
Nozzle diameter (1/100 mm)
48
100
54
85
Reduced flow rate (MJ/h)
1.4
5.4
1.4
2.9
See General safety instructions.
The values indicated refer to the cross-
section of the internal conductor.