Smeg L23 CLASSIC Installation And User Instructions Manual Download Page 1

INSTALLATION & USER INSTRUCTIONS

All instructions must be handed to the user for safekeeping.

Revision A - 08/07

Country(s) of destination - GB/IE

L30 FAB 

P23 LINEAR, P23 CLASSIC

L23 LINEAR, L23 CLASSIC

MODELS

WALL MOUNTED HIGH EFFICIENCY GAS FIRE

SMEG (UK) LTD 

3 Milton Park 

Abingdon, Oxon 

OX14 4RN 

Phone: +44 (0)870 99 09 907 

Fax : +44 (0)870 99 09 337 

It is the LAW that all gas appliances and fittings are installed by a competent person (such as a CORGI registered fitter) and in

accordance with the Gas Safety (Installation and Use) Regulations 1998.

Summary of Contents for L23 CLASSIC

Page 1: ...SSIC L23 LINEAR L23 CLASSIC MODELS WALL MOUNTED HIGH EFFICIENCY GAS FIRE SMEG UK LTD 3 Milton Park Abingdon Oxon OX14 4RN Phone 44 0 870 99 09 907 Fax 44 0 870 99 09 337 It is the LAW that all gas appliances and fittings are installed by a competent person such as a CORGI registered fitter and in accordance with the Gas Safety Installation and Use Regulations 1998 ...

Page 2: ...erwise stated all rights including copyright in the text images and layout of this booklet is owned by Smeg UK LTD You are not permit ted to copy or adapt any of the content without the prior written permission of Smeg UK LTD The products covered by this booklet are protected under patent GB2275331B ...

Page 3: ...in the air such as tobacco smoke can dle smoke etc exist may cause the walls to become discoloured This appliance is intended as a secondary source of heat only and should not be used in a room without some form of back ground heating present If the appliance is used in a room as the sole source of heat then condensation may occur on colder sur faces within the room On first light up of a new appl...

Page 4: ...implementation of BS 5871 pt 4 installation in bedrooms is then permit ted If the appliance is to be fitted in a bedroom then an electronic carbon monoxide detector complying with the current edition of BSEN 50291 must be installed in the same room as the appliance For maximum safety it is recommended that such device is continuously mains powered and arranged in such a way that the gas supply to ...

Page 5: ...ould be positioned on the wall above the appliance It should be established that any mirrors or picture frames etc to be positioned on the wall above the appliance are able to withstand prolonged exposure to moderate heat and moisture before proceeding with their installation The back of the appliance may be installed directly onto a combustible wall providing it is relatively flat and does not in...

Page 6: ...ust be secured using suitable clips and protected against corrosion Ideally factory finished protected pipework and fittings should be used Joints should be kept to a minimum and compression fittings must not be used The pipework installation must be tested for tightness before any protection is applied and or the pipework and fittings are buried Remove any protective film coatings from the finish...

Page 7: ...wall fixings Insert the wall fixing screws into the top wall plugs taking care to leave the screws protruding approximately 5mm from the wall Now hang the appliance onto these screws through the two keyhole shaped holes in the upper brackets on the back panel of the appliance Insert the lower fixing screws into the lower wall plugs through the corresponding fixing holes in the lower part of the ba...

Page 8: ...urner pipe next to the brass restrictor connector Remove the burner cover plate to access by removal of the four retaining screws as shown in figure 9 Release the setting pressure test point screw shown in figure 10 and attach a pressure gauge Light the fire on the HIGH set ting To commission the appliance the burner pressure must be in accordance with the figures stated in section 2 0 of these in...

Page 9: ...rdingly the room should be well ventilated with all windows and doors open during this period During this period the appliance may cause smoke alarms to sound If this happens reset the alarms but do not remove the batteries Recommend that a guard be used for the protection of the young pets the elderly and the infirm Isolate the fire from the gas supply Ensure that the fire is fully cold before at...

Page 10: ...nnecting the electrode HT lead gas pipe and unscrewing the mounting screws and lifting away The pilot assembly is a non serviceable item and should not be taken apart Aeration holes must be absolutely clear internally for proper operation NEVER MODIFY OR BEND THETHERMOCOUPLETO MAKETHE PILOT STAY ALIGHT Modifications are dangerous and can have serious unseen effects on safety If the pilot will not ...

Page 11: ...Examples 35ppm 0 0035 15ppm 0 0015 5ppm 0 0005 Now divide the concentration of carbon monoxide CO expressed in percent by the concentration of carbon dioxide CO2 to obtain the appliance combustion ratio The combustion ratio of the gasses emitted by the catalytic convertor should not exceed 0 0015 If replacing firstly remove the decorative frame glass facia as described in section 8 4 The catalysts...

Page 12: ...s for a time and then cuts off Loose or faulty thermocouple rectify Blocked pilot clean out Dirt or lint in pilot aeration hole or on the lint gauze clean thoroughly If the pilot will not stay lit there is a problem with dirt the gas supply or the thermocouple needs replacement Modifications are dangerous and can have a serious unseen effect on safety NEVER MODIFY OR BEND THE THERMOCOUPLE TO MAKE ...

Page 13: ... fitted This appliance incorporates a combustion monitoring system ODS DO NOT burn any foreign material on this fire Under no circumstances shall the appliance be used if the glass front door or panel has been removed damaged or is open Do not place any objects on top of the appliance The integral catalysts should be checked by the installer upon servicing to ensure there are no defects or obstruc...

Page 14: ...hat any vapour control bar rier is not damaged and that any structural members of the house frame are not damaged refer to section 7 0 The appliance must not be positioned vertically within 100 mm 4 of a carpeted floor rugs or fabric materials of any kind This dimension is measured vertically to the bottom of the appliance firebox Purpose provided ventilation of 100cm2 is required for this applian...

Page 15: ...l reasons may be suspected If a door or window has been opened creating a draught then pilot disturbance could be the problem and removal of the draught should resolve this The appliance can then be re lit in accordance with the previous section If pilot disturbance is not the cause then the ODS safety system may be in operation Switch the appliance OFF call in your installer to check the applianc...

Page 16: ...r assembly L23 models IN F960003 Inner glass door assembly L30 models FT F730023 Pilot assembly FT003155 2 Gas valve Please Enquire Burner unit FB F780079 Catalyst seal kit must also be supplied IN F940136 Seal kit for Catalyst 4 7 0 SERVICING 8 0 LIST OF REPLACEMENT PARTS 9 0 INSTALLATION DETAILS Model Date installed Fire serial No Name of installer Supplied by Corgi Reg no of installer 10 0 SERV...