Model 3600-I IR3 Flame Detector
Page 56 of 66
Appendix D.1.3. Range
Detector Model
Detector
Sensitivity Setting
Testing Distance
3600-I
50ft (15m)
6.6ft (2m)
100ft (30m)
19.6ft (6m)
150ft (45m)
29.5ft (9m)
200ft (60m)
39.3ft (12m)
Figure 47: Detection Ranges
NOTE
:
The minimum distance from the detector is 30 in (75 cm).
At extreme temperatures, there is a 15% maximum reduction in the testing range.
Important
: Keep the Fire Simulator in a safe place when not in use.
Appendix D.1.4. Charging the Battery
The Flame Simulator uses Lithium Ion batteries as a rechargeable power source. When the batteries are
fully charged, the simulator operates for at least 100 times without recharging. When the voltage from the
batteries is lower than the required operational level, the simulator will not operate.
NOTE: The following instructions heavily reference
(found in the General Reference Diagram portion of this section) to locate parts. For any
reference to
the two additional figures (
) can be used to
see
different angles of the same parts (the item #’s reference the same parts for these
uses a different item to part number identification schema).
➣
To charge the battery:
1. Place the Flame Simulator on a table in a safe area, not exceeding 40°C.
2. Release the locking screw (item 8,
).
3. Unscrew the battery back cover (item 3,
) counter-clockwise.
4. Unscrew the locking disc clockwise (item 4,
).
5. Pull out the battery (item 2,
) from the Flame Simulator.
6. Connect the battery to the charger. Verify that the charger is the one supplied with the
flame simulator model FRIWO MPP15 with maximum charging voltage of 16.8V (4.2 V x
4) with a maximum current of 700mA.
7. Charge for a maximum of 2
– 3 hours, until the green LED on the charger turns on.
8. Disconnect the charger.
9. Insert the battery (item 2,
) to the Flame Simulator.
10. Screw the locking disc (item 4,
).
11. Screw the back cover (item 3,
).
12. Lock the back cover with the locking screw (item 8,
).