No.VQC4000V-OMX0001

 

Trouble 

When the valve is failing, use this flow chart to 
clarify the cause of the failure and take 
countermeasures appropriate for the cause. 

Possible cause 

Countermeasures 

Operating 

failure 

The air 

supply 

does not 

switch the 

valve

 

1) Sliding failure or stick of 
main valve. 
A foreign material included in 
supplied air is caught by main 
valve and makes the main 
valve unable to slide smoothly 
or sticky. 

 Replace with new valve. 

 Clean the supplied air. 

2) Pressure drop. 
The pressure of supplied air 
lowers the valve which can 
operate the valve (min. 
operating pressure). 

Raise the pressure of supplied air up 
to operating pressure of the valve. 

1) Failure of electrical system   

 Incorrect wiring 

 Blow of fuse and breakage of 

lead wire. 

 Poor contact at contactor wire 

or connection part 

 Failure of sequencer 

 Lack of supply voltage 

Check these items and replace part 
and re-wire positively.

 

1) Voltage drop 
Even if the indicator light keeps 
turning on, the valve can’t be 
operated due to the voltage 
drop. 

 Check the voltage and if it is not 

enough to operate the valve, take 
appropriate measures. 

2) Leakage current 
When the power turns off, the 
valve can’t be switched due to 
residual voltage. 

 Confirm the residual voltage is 

follows. 

 DC is 3% or less of rated voltage. 

3) Failure of pilot valve 

 Foreign matter caught in 

  core of pilot valve. 

 Disconnection coil   

  wire of pilot valve 

 Swelled out poppet 

  of pilot valve 

 Burnt coil of pilot valve 

 

(Higher voltage or wrong coil 

used, Coil splashed by 
water) 

 
 

 Replace part or re-wire positively. 

 Check voltage. Replace valve. 

  (Pilot valve) 
 
 

 Replace valve (pilot valve). Protect 

the valve so that water does not 
splash the coil. 

Response 

failure 

   

The 

operation 

of the valve 

is delay.

 

 

1) Current leakage 
  When the power turns off, the 
valve can be switched late due 
to residual voltage. 

 Confirm the residual voltage is 

follows. 

 DC is 3% or less of rated voltage. 

2) Clogging of filter element of 
manifold. 

 Clean the element or replace with 

new element.   

3)  Sliding failure or stick of 
main valve. 
A foreign material included in 
supplied air is caught by main 
valve and makes the main 
valve unable to slide smoothly 
or sticky. 

 Replace with new valve. 

 Clean the supplied air. 

 

 
 
 
 

 

 

 

Can manual 
override move the 
valve 

NO 

YES 

Does the indicator 
light keep turning on 
during 
energization? 

NO 

YES 

Summary of Contents for VQC4000

Page 1: ...Doc No VQC4000V OMX0001 Solenoid Valve PRODUCT NAME VQC4000Series Pilot Valve V100 MODEL Series Product Number...

Page 2: ...ubrication 7 Air Supply 7 Operating Environment 8 Maintenance 8 Specific Product Precautions 9 10 Manifold option Assembly Part No 11 Construction 12 List of valves options and Mounting Bolts 13 Elect...

Page 3: ...equipment failure when configuring the equipment 2 Only personnel with appropriate training should operate machinery and equipment The product specified here may become unsafe if handled incorrectly T...

Page 4: ...failure of the product 3 Prior to using SMC products please read and understand the warranty terms and disclaimers noted in the specified catalog for the particular products 2 Vacuum pads are excluded...

Page 5: ...or other foreign matter from entering inside the valve In addition at the time of vacuum adsorption be sure to supply a constant supply of vacuum Failure to do so may result in foreign matter stickin...

Page 6: ...status by the breakage If the energizing continues in this status a large current flows This may cause secondary damage to the output circuit external peripheral device or valve and may also cause fi...

Page 7: ...nce activities When installing the products allow access for maintenance 3 Tighten threads with the proper tightening torque When installing the products follow the listed torque specifications 4 If a...

Page 8: ...non lube state This prevents accumulation of oil inside the pilot valve Air Supply 1 Type of fluids Please consult with SMC when using the product in applications other than compressed air 2 When ther...

Page 9: ...supply exhaust of compressed air Before components are removed first confirm that measures are in place to prevent workpieces from dropping run away equipment etc Then cut off the supply air and elect...

Page 10: ...h your finger until it stops and turn it clockwise 90 to lock it Turn it counterclockwise to release it Do not apply excessive torque when turning the manual override 0 1 N m or less Valve Mounting Af...

Page 11: ...l the cover hook locks without twisting the protective O ring When pushed in the hook opens and locks automatically Replacement of Pilot Valve Removal Remove the mounting screw that holds the pilot va...

Page 12: ...11 VQC4000V OMX0001 Manifold Options Manifold Assembly Part No...

Page 13: ...12 VQC4000V OMX0001 Construction...

Page 14: ...13 VQC4000V OMX0001 List of Valves Options and Mounting Bolts...

Page 15: ...14 VQC4000V OMX0001...

Page 16: ...15 VQC4000V OMX0001...

Page 17: ...16 VQC4000V OMX0001...

Page 18: ...17 VQC4000V OMX0001...

Page 19: ...18 VQC4000V OMX0001...

Page 20: ...enough to operate the valve take appropriate measures 2 Leakage current When the power turns off the valve can t be switched due to residual voltage Confirm the residual voltage is follows DC is 3 or...

Page 21: ...law 2 3 Tube is cut diagonally Check these items and replace part and re wire positively 2 4 Packing of one touch fitting is damaged Replace with one touch fitting 3 Air leaks through exhaust port R p...

Page 22: ...hiyoda ku Tokyo 101 0021 JAPAN Tel 81 3 5207 8249 Fax 81 3 5298 5362 URL http www smcworld com Note Specifications are subject to change without prior notice and any obligation on the part of the manu...

Reviews: