Installation and Maintenance Manual
Series VQ0000/1000/2000 Series Solenoid Valve,
Body Ported Type (Metal/Rubber Seal)

This manual should be read in conjunction with the current valve catalogue

For future reference, please keep this manual in a safe place

Safety Instructions

These safety instructions are intended to prevent a hazardous situa-
tion and/or equipment damage.These instructions indicate the level
of potential hazard by label of “Caution”, “Warning” or “Danger”.
To ensure safety, be sure to observe ISO4414 

(Note1)

, JIS B 8370 

(Note2)

and other safety practices.
Note 1: ISO 4414: Pneumatic fluid power – Recommendations for the
application of equipment to transmission and control systems.
Note 2: JIS B 8370: Pneumatic system axiom.

CAUTION :

Operator error could result in injury or

equipment damage.

WARNING :

Operator error could result in serious

injury or loss of life.

DANGER :

In extreme conditions, there is a 

possible result of serious injury or loss of life.

WARNING

1. The compatibility of pneumatic equipment is the respon-

sibility of the person who designs the pneumatic system
or decides its specifications.

Since the products specified here are used in various operating
conditions, their compatibility for the specific pneumatic system
must be based on specifications or after analysis and/or tests to
meet your specific requirements.

2. Only trained personnel should operate pneumatically

operated machinery and equipment.

Compressed air can be dangerous if an operator is unfamiliar 
with it. Assembly, handling or repair of pneumatic systems should
be performed by trained and experienced operators.

3. Do not service machinery/equipment or attempt to

remove component until safety is confirmed.

1)  Inspection and maintenance of machinery/equipment should

only be performed after confirmation of safe locked-out 
control positions.

2)  When equipment is to be removed, confirm the safety process

as mentioned above. Switch off air and electrical supplies and
exhaust all residual compressed air in the system.

3)  Before machinery/equipment is re-started, ensure all safety

measures to prevent sudden movement of cylinders etc.
(Bleed air into the system gradually to create back-pressure,
i.e. incorporate a soft-start valve).

4. Contact SMC if the product is to be used in any of the 

following conditions:

1)  Conditions and environments beyond the given specifica-

tions, or if product is used outdoors.

2)  Installations in conjunction with atomic energy, railway, air

navigation, vehicles, medical equipment, food and beverage,
recreation equipment, emergency stop circuits, press 
applications, or safety equipment.

3)  An application which has the possibility of having negative

effects on people, property, or animals, requiring special 
safety analysis.

CAUTION

Ensure that the air supply system is filtered to 5 micron.

Standard specifications (Fig 2)

Type of seal

Metal seal

Rubber seal

Fluid

Air • Inert gas

Air • Inert gas

Note3)

Max. operating pressure

0.7MPa (High pressure type: 0.8MPa)

Valve specifications

Min. operating pressure

Single

0.1MPa (1.0 kgf/cm

2

)

0.15MPa (1.5 kgf/cm

2

)

Double 

0.18MPa (1.8 kgf/cm

2

)

0.18MPa (1.8 kgf/cm

2

)

(latching)

3 position

0.1MPa (1.0 kgf/cm

2

)

0.2MPa (2.0 kgf/cm

2

)

Proof pressure

1.5MPa (15.3 kgf/cm

2

)

Ambient and fluid temperature

-10~+50°C 

Note 1)

-5~+50°C 

Note 1)

Lubrication

Not required

Manual override

Note 2) 

Non-locking push type/push-locking 

tool, lever types (option)

Protection structure

IP40

Coil rated voltage

12, 24VDC

Allowable voltage

±10% of rated voltage

Solenoid

Type of coil insulation

Class B

specifications

Power consumption

24VDC

1WDC (42mA),

Note 3)

1.5WDC (63mA),

Note 4)

0.5WDC (21mA)

(current value)

12VDC

1WDC (83mA),

Note 3)

1.5WDC (125mA),

Note 4)

0.5WDC (42mA)

Note 1: Use dry air to prevent dew condensation when operating at low temperature.
Note 2: Push-locking type (B) or (C) should be selected for double (latching) type.
Note 3: Value for low-wattage (0.5W) specifications.
Note 4: Value for high-pressure (1.5W) type specifications.

Tube connection (push-in fitting) (Fig 5)

Ensure that the end of the tube is cut square. Push the tube firmly into
the fitting until it stops. Pull back on the tube to ensure that it is
engaged.

Replacement of cylinder port fittings

The cylinder port fittings are of a cassette type for easy replacement
(except for VQ0000). The fittings are blocked by a clip inserted from
the top of the valve. Remove the clip with a screwdriver to remove fit-
tings. To replace, insert the fitting assembly until it strikes against the
inside wall and then re-insert the clip to the specified position.

Disconnection

Push down on the collet flange, hold down, and withdraw the tube.

Electrical connection, plug lead only (plug connector) (Fig 4)

Push the connector onto the pins of the solenoid valve in a straight
line, ensuring that the lip of the lever is securely positioned in the
groove of the solenoid cover.

Disconnection (Fig 4)

Press the lever against the connector and pull the connector in a
straight line away from the solenoid.

NOTE

Plug-in units are factory pre-wired to specification (Fig 8).

Electrical disconnection D-sub connector (Fig 8)

Loosen the two captive screws 

1

, pull off the connector 

2

.

Electrical re-connection of D-sub connector (Fig 8)

Insert connector 

2

into the body 

3

.

CAUTION

Ensure that the connector enters directly onto the pins in the body.
Tighten the two retaining screws 

1

.

Electrical dis-connection flat cable connector (Fig 11)

Lift the two clamps 

1

outwards from the connector 

2

.

Remove the connector 

2

out of the body 

3

.

Re-fitting is the reverse of the above.

Wiring

Ensure that control wiring is separated from power wiring to prevent
noise generation.

Manual override

WARNING

Exercise extreme CAUTION when operating solenoid valve manual
overrides as connected equipment will commence operation.

Push non-locking type (Fig 6)

Push down on the manual override button 

1

until it stops (ON). Hold

this position whilst carrying out function checks. Release the manual
override button and the override will re-set to the (OFF) position.

Push locking type manual override (Fig 6)

Push down on the manual override button, using a small screwdriver
until it stops. Turn the button through 90° clockwise to lock. (180°
VQ0000).

CAUTION

In this position the override will be mechanically 'locked' in the ON
position.

Un-locking

Turn the manual override using a small screwdriver through 90° (180°
VQ0000) anti-clockwise. Remove the screwdriver and the manual
override will re-set.

Raised button type locking override (Fig 6)

Push down on the raised button until it stops. Turn the button through
90° clockwise by hand.

CAUTION

In this position the override is mechanically 'locked' in the ON 
position.

Un-locking manual override

Turn the raised button through 90° anti-clockwise by hand. Release
the button and the manual override will re-set to the OFF position.

Lamp and surge voltage suppressor (Fig 7)

All solenoid valves are equipped with lamp and surge protection as a
standard feature. The indicators are positioned on one end of the
valve, for both single and double solenoid types. The colours of the
indicator lamps match the colours of the manual override buttons.

D-sub connector/flat cable connector/terminal block

Wiring specification (Fig 12)

With the A side solenoid of the 1st station, as No. 1 (i.e. connected to

No. 1 terminal), wires are connected in the order indicated by the
arrow in Fig 12.

NOTE: No terminal should be left vacant.

Maintenance

WARNING

Before carrying out any maintenance work ensure that air and power
supplies are ISOLATED.

Plug lead unit/flip type

Removal of a Valve (Fig 5b)

1. Disconnect electrical connector. (See above.) 
2. Slacken lower tie bolt 

3

2~3 turns. Remove the upper tie bolt 

6

and retain. Separate the valves either side of the valve to be
removed approximately 2mm. Lift the valve to be changed off the
manifold, in the direction of the arrow 

J

.

Replacing a valve (Fig 5b)

Reverse the above procedure to replace a valve.

023a/eng

Installation

CAUTION 

Ensure all air and power supplies are isolated before commencing
installation.

WARNING

DO NOT INSTALL THESE VALVES IN EXPLOSIVE ATMOSPHERES.
If these valves are exposed to water or oil droplets, ensure that the
valves are protected.
If it is intended to energise a valve for an extended period please 
consult SMC.

Fig 1

Symbol

2 position single

3 position closed centre

3 position exhaust centre

3 position pressure centre

2 position double (latching)

Metal 
seal

Rubber
seal

Plug lead unit/flip type (Fig 3)

Fig 3

Fig 5

Fig 12

Fig 6

Fig 11

Fig 8

Fig 4

Fig 7

Note 1: A-side energization: A light (orange) illuminates. B-side energization: B light (green) illuminates.

Equipped with a wiring error prevention (stop diode) mechanism and a surge absorption (ZNR/surge absorption
diode) mechanism.

Note 2: Applicable to negative COM specification models.
Note 3: In case of double (latching), the electromagnetic valve channel is, A- (set): P

R

A, B

R

R, (B- (reset): P

R

B, A

R

R

Connector 
assembly

Connector 
assembly

Connector 
assembly

Type of 
connection

Type of 
connection

Type of 
connection

P port

P port

P port

R port

R port

R port

A, B port

A, B port

A, B port

25-pin

VV5Q24

VV5Q14

VV5Q04

Cover

Cover

Groove

Lever

Hook

Connector
AXT661-12

DC indicator

Socket
DXT170-71-1

Lead wire
0.2~0.33mm

2

(Max. O.D.
: ø1.7mm)

Groove

Pin

Pin

Type of connection

25-pin

Clip

Fittings assembly

P port

R port

A, B port

3

3

2

2

1

1

Cable 
assembly

Electrical wiring specifications

D side

U side

1 2 3 -------------Stations

Non-locking push type

Push-locking tool type

Push-locking lever type

Bore: ø3.2

Bore: ø3.2

10 mm

3

2

1

Manual override: Orange

Single 
solenoid type

Double
(latching)
type

Indicator light
A: Orange
B: Green

Indicator light
Orange

Manual override: Green

DC type circuit diagram

Single solenoid type (DC)

Double (latching) solenoid 

type (DC)

A (-)

A -(Set)

C +(Com)

B - (Reset)

C(+)

Light

ZNR

SOL

SOL

Protection circuit

COM

COM

COM

COM

COM

F kit

D-sub connector

(In case of 25-pin)

P kit

Flat cable 
connector

(In case of 26-pin)

T kit

Terminal block

(In case of 

16 terminals)