background image

 

- - 7 - -

 

- 7 - 

 

VFR6000-OMA0001-B

 

 

 

 
 
 

 
1.  When  extremely  dry  air  is  used  as  a  fluid, 

degradation  of  the  lubrication  properties  inside 

the  equipment  may  occur,  resulting  in  reduced 

reliability  (or  reduced  service  life)  of  the  equip- 

ment. Please consult with SMC. 

2. Install an air filters. 

Install  an  air  filter  upstream  near  the  valve.  Select  an  air 

filter with a filtration size of 5

µ

m

 

or smaller. 

3. Take measures to ensure air quality, such as by 

installing  an  aftercooler,  air  dryer,  or  water 

separator. 

Compressed  air  that  contains  a  large  amount  of  drainage 

can  cause  malfunction  of  pneumatic  equipment  such  as 

valves.  Therefore,  take  appropriate  measures  to  ensure 

air quality, such as by providing an aftercooler, air dryer, or 

water separator. 

4.  If  excessive  carbon  powder  is  seen,  install  a 

mist  separator  on  the  upstream  side  of  the 

valve.

 

If  excessive  carbon  powder  is  generated  by  the 

compressor,  it  may  adhere  to  the  inside  of  a  valve  and 

cause it to malfunction. 

For compressed air quality, refer to SMC’s Best Pneumatics 

catalog. 

 

Operating Environment 

 
 
 
 

1.  Do  not  use  in  an  atmosphere  having  corrosive 

gases, chemicals, sea water, water, water steam, 

or  where  there  is  direct  contact  with  any  of 

these.   

2. Do not use in an environment where flammable 

gas or explosive gas exists. Usage may cause a 

fire  or  explosion.  The  products  do  not  have  an 

explosion proof construction. 

3. Do not use in a place subject to heavy vibration 

and/or shock.   

4.  The  valve  should  not  be  exposed  to  prolonged 

sunlight. Use a protective cover. 

5. Remove any sources of excessive heat. 

6.  If  it  is  used  in  an  environment  where  there  is 

possible  contact  with  oil,  weld  spatter,  etc., 

exercise preventive measures. 

 

 

7. When the solenoid valve is mounted in a control 

panel or its energized for a long time, make sure 

ambient  temperatures  is  within  the  specification 

of the valve. 

 

Maintenance 

 
 

 

1.  Perform  maintenance  inspection  according  to 

the  procedures  indicated  in  the  operation 

manual. 

If  handled  Improperly,  malfunction  and  damage  of 

machinery or equipment may occur. 

2.   Removal  of  equipment,  and  supply / exhaust  of 

compressed air 

When  components  are  removed,  first  confirm  that 

measures are in place to prevent workpieces from dropping,     

run-away equipment, etc. Then, cut off the supply pressure 

and electric power, and exhaust all compressed air from the 

system using the residual pressure release function. 

For  3-position  closed  center  type,  exhaust  the  residual 

pressure between the valve and the cylinder. 

When  the  equipment  is  operated  after  remounting  or 

replacement,  first  confirm  that  measures  are  in  place  to 

prevent  lurching  of  actuators,  etc.  Then,  confirm  that  the 

equipment is operating normally. 

3. Low frequency operation 

Valves should  be  operated  at  least  once  every  30  days to 

prevent malfunction. (Use caution regarding the air supply.) 

4. Manual override 

When  the  manual  override  is  operated,  equipment  will  be 

actuated. 

Operate after safety is confirmed. 

 

 

 

1. Drain flushing 

Remove drainage from the air filters regularly. 

2. Lubrication 

In  the  case  of  rubber  seals,  once  lubrication  has  been 

started, it must be continued. 

Use  class  1  turbine  oil  (with  no  additive),  ISO  VG32 

because  if  other  lubricant  oil  is  used,  it  may  cause 

malfunction.  Please  contact  SMC  for  suggested  class  2 

turbine oil (with additive), ISO VG32. 

Air Supply 

Warning 

 

 

Warning 

 

Caution 

Caution 

 

VFR6000  Series 

5 Port Solenoid Valve / Precautions 4

    

 

Be sure to read before handling.

    

Summary of Contents for VFR6 00 Series

Page 1: ...Doc No VFR6000 OMA0001 B 5 Port Solenoid Valve PRODUCT NAME VFR6000 Series MODEL Series...

Page 2: ...afety Instructions 2 3 Precautions on Design 4 5 Selection 4 5 Mounting 5 Piping 6 Wiring 6 Lubrication 6 Air Supply 6 7 Operating Environment 7 Maintenance 7 Specific Product Precautions 8 9 10 Troub...

Page 3: ...of equipment failure when configuring the equipment 2 Only personnel with appropriate training should operate machinery and equipment The product specified here may become unsafe if handled incorrect...

Page 4: ...placement product or necessary parts will be provided This limited warranty applies only to our product independently and not to any other damage incurred due to the failure of the product 3 Prior to...

Page 5: ...on closed center valve or double check valve type ensure that the residual pressure between the valve and the cylinder is released 7 Double solenoid type When using the double solenoid type for the fi...

Page 6: ...voltage will remain Therefore take into consideration the surge voltage protection of the controller In the case of diodes the residual voltage is appro ximately 1V 5 Operation in a low temperature c...

Page 7: ...does not require any further 2 If a lubricant is used in the system use class 1 turbine oil no additive ISO VG32 Once a lubricant is used in the system lubrication must be continued because the origi...

Page 8: ...e contact with oil weld spatter etc exercise preventive measures 7 When the solenoid valve is mounted in a control panel or its energized for a long time make sure ambient temperatures is within the s...

Page 9: ...le cable Cross section of the wire 0 5 to 1 5mm2 Cable O D 8 to 10mm Applicable terminal 1 25Y 3L 1 25 3 5S 1 25 4M Terminal block type Remove cover 1 over terminal block 2 attached to the inside of b...

Page 10: ...id valve Loosen set screw and take solenoid valve out vertically otherwise it may cause damage to the solenoid valve Never remove valve at an angle When mounting solenoid valve on to the base plug pin...

Page 11: ...assembly like the following figure Note Do not change the rated voltage Change Direction of DIN Connector Cable Entry Unscrew retaining screw pull off outer cover rotate connector block through 180o...

Page 12: ...t specification Remedy Spool valve has not completely shifted 1 2 3 4 6 Coil splashed by water Low pilot pressure Intrusion of foreign matter Leakage Worn spool packing Poor seal on actuator cylinder...

Page 13: ...ve assembly 11 To remove foreign matter clean the pipe by air blow Replace valve 12 Repair or replace actuators Isolate the valve and re tighten the bolts 13 If no improvement is achieced in spite of...