PSE510-TF2Z047EN
Page 1 of 2
Instruction Manual
Pressure Sensor
PSE510 / PSE511 / PSE512
The intended use of the pressure sensor is to measure the pressure of
fluids and provide an analogue output signal.
1 Safety Instructions
These safety instructions are intended to prevent hazardous situations
and/or equipment damage. These instructions indicate the level of
potential hazard with the labels of “Caution,” “Warning” or “Danger.”
They are all important notes for safety and must be followed in addition
to International Standards (ISO/IEC)
*1)
, and other safety regulations.
*1)
ISO 4414: Pneumatic fluid power - General rules relating to systems.
ISO 4413: Hydraulic fluid power - General rules relating to systems.
IEC 60204-1: Safety of machinery - Electrical equipment of machines.
(Part 1: General requirements)
ISO 10218-1: Manipulating industrial robots –Safety, etc.
•
Refer to the product catalogue, operation manual and handling
precautions for SMC products for additional information.
•
Keep this manual in a safe place for future reference.
•
To ensure safety of personnel and equipment the safety instructions in
this manual must be observed, along with other relevant safety
practices.
Caution
Caution indicates a hazard with a low level of risk
which, if not avoided, could result in minor or
moderate injury.
Warning
Warning indicates a hazard with a medium level
of risk which, if not avoided, could result in death
or serious injury.
Danger
Danger indicates a hazard with a high level of risk
which, if not avoided, will result in death or
serious injury.
Warning
•
Ensure compliance with relevant safety laws and standards.
All work must be carried out in a safe manner by a qualified person in
compliance with applicable national regulations.
2 Specifications
2.1 General Specifications
2.2 Piping and Weight specification
Model
R06
M5
01
T01
Port size
6 mm
reducer
M5 x 0.8
R(PT) 1/8
M5 x 0.8
NPTF 1/8
M5 x 0.8
Material of case
Resin: PBT
Material of fitting
-
SUS303
C3604BD (electroless
nickel plating)
Material of parts
in contact with
fluid
Pressure sensor: Silicon, O ring: NBR
Weight (without
lead wire)
7 g
10 g
12 g
2.3 Cable Specification
Wire Cross section
0.15 mm
2
Wire Colours
Brown, Blue, Black
Sheath material
Oil resistant vinyl cabtyre cable
Outside diameter
2.55 mm
Cable Length
3 m
Warning
•
Special products (-X) might have specifications which are different
from those shown in this section. Contact SMC for specific drawings.
2 Specifications (continued)
2.4 Analogue Output
Model
Operating
pressure range
A
B
C
PSE510-#
0 to 1 MPa
0
1 MPa
-0.1
MPa
PSE511-#
0 to -101 kPa
0
-101 kPa
10.1
kPa
PSE512-#
0 to 100 kPa
0 kPa
100 kPa
-
3 Installation
Warning
Do not install the product unless the safety instructions have been read
and understood.
3.1 Piping
Caution
•
Before piping make sure to clean up chips, cutting oil, dust etc.
•
When installing piping or fittings, ensure sealant material does not
enter inside the port. When using seal tape, leave 1.5 to 2 threads
exposed on the end of the pipe/fitting.
•
Tighten fittings according to the specified tightening torque.
Thread size
Tightening Torque
R1/8, NPT1/8
7 to 9 N•m
M5 x 0.8
1/6 rotation after tightening by hand
•
Only fluids which are non-corrosive to SUS303, C3604BD, and NBR
should be used.
•
Install the piping correctly in a safe place away from water and dust.
•
When piping, apply a spanner to the piping section of the sensor.
•
For one touch fittings, insert the tube into the sensor fitting carefully
and securely all the way to the bottom.
3.2 Environment
Warning
•
Do not use in an environment where corrosive gases, chemicals, salt
water or steam are present.
•
Do not use in an explosive atmosphere.
•
Do not expose to direct sunlight. Use a suitable protective cover.
•
Do not install in a location subject to vibration or impact in excess of
the product’s specifications.
•
Do not mount in a location exposed to radiant heat that would result in
temperatures in excess of the product’s specifications.
4 Wiring
4.1 Internal circuit and wiring
•
Output specification
Voltage output: 1 to 5 V
Output impedance: Approx. 1 kΩ
4.2 Attaching a sensor connector to the lead wire
•
The sensor wire sheath should be stripped as shown in the figure.
•
Do not cut the insulation.
•
The corresponding wire colour shown in the table should be pushed
fully into the correct pin number marked on the sensor connector.
Pin No.
Wire colour
1
Brown (DC+)
2
N.C.
3
Blue (DC-)
4
Black (1 to 5 V)
•
Check that the above preparation has been performed correctly, then
press part A by hand to make a temporary connection.
•
Press part A fully home using a suitable tool.
•
The sensor connectors cannot be re-used once they have been
pressed fully closed. If connection failure or incorrect wiring occurs a
new sensor connector must be used.
•
When connecting the sensor to a PSE200 / PSE300 series monitor,
use the connector for sensor lead wire (ZS-28-C) or an e-Con*
connector from the table below.
Maker
Model No.
Sumitomo 3M
37104-3101-000FL
Tyco Electronics
1-1473562-4
OMRON
XN2A-1430
* Refer to the manufacturers e-Con connector catalogue.
Analogue
output [V]
Pressure
1 to 5 VDC
ORIGINAL INSTRUCTIONS
Model
PSE510-#
PSE511-#
PSE512-#
Operating Pressure
range
0 to 1 MPa
0 to -101
kPa
0 to 100 kPa
Maximum Operating
Pressure
1 MPa
200 kPa
Applicable Fluid
Air, non-corrosive gas
Power supply
voltage
12 to 24 VDC ±10%
(with 10% max. voltage ripple)
Current consumption
10 mA or less
Analogue output
specification
1 to 5 VDC
Load impedance:
≥
1 kΩ
Repeatability
± 0.3% F.S.
Temperature
characteristics
±1% F.S. (at 25°C ±10°C)
±1.5% F.S. (between 0 to 50°C)
E
nv
ir
onm
en
tal
Enclosure
IP40
Ambient
temperature
range
Operation: 0 to 50°C
Storage: -20 to 70°C
(no condensation or freezing)
Ambient
humidity
Operation, Storage: 35 to 85% RH
(no condensation)
Withstand
voltage
1000 VAC or more (50/60 Hz), 1 minute
(between wires and case)
Insulation
resistance
2 MΩ or more at 500 VDC
(between wires and case)
Vibration
resistance
10 to 500 Hz either smaller of vibration
amplitude 1.5 mm or acceleration 10 G
2 hours in X, Y, Z direction
Shock
resistance
100 G, 3 times in X, Y, Z direction
(Analogue output)