Other Functions
○Snap shot function
The current flow/temperature value can be stored to the switch output ON/OFF set point.
When the items of sub screen (left side) below are selected in 3 step setting mode, simple setting mode or
function selection mode ([F 1] Setting of OUT1, [F 2] Setting of OUT2), by pressing the UP and DOWN
buttons simultaneously for 1 second or longer, the value of the sub screen (right side) shows [- - -], and then
values corresponding to the current flow are automatically displayed.
Output mode
Configurable items
Sub screen (left side)
Snap shot function
Hysteresis mode
Set value
(
)/
(
)
○
Hysteresis
/
○
Window comparator mode
Set value
(
),
(
)
(
),
(
)
○
Hysteresis
/
×
•Set value
The value is set to the same value as the display value (current flow).
(There is a range which cannot be set to the current flow depending on the hysteresis. In that case, the
value is set to the closest value.)
•Hysteresis
The hysteresis is calculated from the equation below and set.
Normal output: (set value) - (current flow)
Reverse output: (current flow) - (set value)
If the calculation result becomes 0 or less, [Err] is displayed on the sub screen (right side) and the set value
is not changed.
Afterwards, it is possible to adjust the value by pressing the UP or DOWN button.
○Peak/bottom value indication
The maximum (minimum) flow when the power is supplied is detected and updated.
In peak/bottom indication mode, the current pressure is displayed.
Press the UP or DOWN button in measurement mode to switch the sub screen (left side) to the display shown
below.
Peak/bottom values are displayed on the sub screen (right side) at the same time as the current flow on the
main screen.
Peak/Bottom value is cleared if the power supply is disconnected.
When the SET and DOWN buttons are pressed for 1 second or longer simultaneously while the peak/bottom
values are displayed, the sub screen (right side) displays [- - -] and the maximum (minimum) flow are cleared.