-20-
No.PF
※※
-OMY0002
■
Wiring
Connection
Connections should only be made with the power supply turned off.
Use a separate route for the product wiring and any power or high voltage wiring. Otherwise, malfunction
may result due to noise.
Ensure that the FG terminal is connected to ground when using a commercially available switch-mode
power supply. When a switch-mode power supply is connected to the product, switching noise will be
superimposed and the product specification can no longer be met. This can be prevented by inserting a
noise filter, such as a line noise filter and ferrite core, between the switch-mode power supply and the
product or by using a series power supply instead of a switch-mode power supply.
Connecting/Disconnecting
Align the lead wire connector with the connector key groove, and insert it straight in. When the knurled part
is fully tightened. Check that the connection is not loose.
When removing the connector, unlock the knurled part and pull out the connector straight.
Connector pin numbers (lead wire)
Used as switch output device
No.
Name
Lead wire colour
Function
1
DC(+)
Brown
12 to 24 VDC
2
N.C./OUT2
White
Not connected/Switch output 2 (SIO)/Analogue output/External input
3
DC(-)
Blue
0 V
4
OUT1
Black
Switch output 1
Used as IO-Link device
No.
Name
Lead wire colour
Function
1
L+
Brown
18 to 30 VDC
2
N.C./OUT2
White
Not connected/Switch output 2 (SIO)/Analogue output/External input
3
L-
Blue
0 V
4
C/Q
Black
Communication data (IO-Link)/Switch output 1 (SIO)
: When using the lead wire with M8 connector included with the PFMC7 series.