background image

Piping for the One-touch fitting

•Insert the tube all the way into the fitting

so that it cannot be pulled out.

•Insertion with excessive force can cause

damage.

•Ensure there is no leakage after piping.

•Use the product within the specified

operating pressure and temperature range.

Troubleshooting

: If the error cannot be reset after the above measures are taken, then please contact SMC.

Instantaneous
flow error

The flow has exceeded the upper limit of the
flow display range.

Reduce the flow.

Error name

Error display

Description

Measures

OUT1 over
current error

The switch output (OUT1) load current has
exceeded 80 mA.
The switch output (OUT2) load current has
exceeded 80 mA.

Turn the power OFF and
remove the cause of the over
current. Then turn the power
ON again.

System error

An internal data error has occurred.

Turn the power OFF and turn
it ON again.

The accumulated flow has reached the set
accumulated flow value.
(For count down display)

The accumulated flow has exceeded the
accumulated flow range.
(For count up display)

Fluid is flowing in the reverse direction by at
least -5% of the maximum rated flow value.

Connect the fluid flow in the
correct direction.

Reset the accumulated flow.
(Press the 

and 

buttons

simultaneously for 1 second
or longer)

Specifications / Dimensions

Refer to the product catalogue or operation manual from SMC website 

(URL http://www.smcworld.com) for more information about the product specifications and

dimensions.

Note: Specifications are subject to change without prior notice and any obligation on the part of the manufacturer.
© 2011-2015 SMC Corporation All Rights Reserved

Akihabara UDX 15F, 4-14-1, Sotokanda, Chiyoda-ku, Tokyo 101-0021, JAPAN

Phone: +81 3-5207-8249   Fax: +81 3-5298-5362

URL http://www.smcworld.com

Refer to the operation manual from SMC website (URL http://www.smcworld.com) for more

information about troubleshooting.

Function Setting

Measurement

mode

Function selection mode

Setting

F0

Setting

F1

Setting

F99

S

S

S

S

S

S

Press the S button

for 2 seconds

or longer.

Press the S button once in measurement mode.

[P_1] or [n_1] and [the current set value] are displayed in turn.

Displayed

in turn

Set value

S

S

S

S

: For models with switch outputs for both OUT1 and OUT2, [P_2] or [n_2] will be displayed too.

Set as above.

: If a mode other than Hysteresis Mode is selected, refer to the operation manual from SMC website

(URL http://www.smcworld.com) or contact SMC.

: Note that the set value and hysteresis settings are limited by each other.

<Operation>

(The illustration shows PFMB7201, when not using the reversed display function.)

Press the 

or 

button to change the set value.

The 

button is to increase and the 

button is to decrease the set value.

S

S

S

S

S

S

Press the

button continuously

to keep increasing the set value.

Press the S button to complete the setting.

Return to measurement mode.

SS

SS

S

S

Item

[F 0]

[F 1]

[ Un i] Unit selection function

1

[ oU1] Output mode of OUT1

[ 1ot] Switch operation of OUT1

[ H_1] Hysteresis of OUT1

Default setting

[

L] L/min

[HYS] Hysteresis mode

[1_P] Normal output

[ 100] 100 L/min (PFMB7201)

[ 10] 10 L/min (PFMB7201)

[ CoL] Display colour of OUT1

[SoG] Green when ON, Red when OFF

[F 2]

[  oU2] Output mode of OUT2 

2

[ 2ot] Switch operation of OUT2

2

[ P_2] Set value of OUT2

2

[HYS] Hysteresis mode

[2_P] Normal output

[F 3]

[ r ES] Response time

[1.0] 1 second

[F10]

[ FLo] Display mode

[ inS] Display instantaneous flow

[F20]

[r AC] Accumulated flow external reset

[F22]

[  F rE] Setting of analogue output 

4

[oFF] Variable range OFF

[F30]

[  SAv] Accumulated value hold

[oFF] Not held

[F31]

[ PoS] Orientation

[Hor ] Horizontal mounting

[ Pr S] Supply pressure

[F80]

[ dSP] Display OFF mode

[F81]

[

P in] Security code

[oFF] Not used

[F90]

[ ALL] Setting of all functions

[F98]

[ tESt] Output check

[F99]

[

in i] Reset to the default settings

[oFF] Reset OFF

[ r EF] Reference condition

[oFF] Not used

[ P_1] Set value of OUT1

[ H_2] Hysteresis of OUT2

2

1: This setting is only available for models with the unit selection function.

2: This setting is only available for models with switch outputs for both OUT1 and OUT2.

3: This setting is only available for models with the external input.

4: This setting is only available for models with the analogue output.

[F13]

[ r Ev] Reversed display mode

[oFF] Unused

[Anr ] Standard condition

Other Functions

Peak/Bottom value display

The maximum (minimum) flow from when the power was supplied to this moment is

detected and updated. In peak/bottom display mode, the maximum (minimum) flow is

displayed

•For peak display, when the 

button is pressed for 1 second or longer,

[the maximum flow] and [Hi] are displayed in turn.

To release holding the display of the maximum flow, press the 

button for 1 second or

longer again to return to measurement mode.

•For bottom display, when the 

button is pressed for 1 second or longer,

[the minimum flow] and [Lo] are displayed in turn.

To release holding the display of the minimum flow, press the 

button for 1 second or

longer again to return to measurement mode.

If the 

and 

buttons are pressed simultaneously for 1 second or longer while the flow

value is being held, the peak (bottom) values are reset.

Reset operation

The accumulated flow value can be reset, when displaying the accumlated flow.

The reset the accumulated flow, press the 

and 

buttons simultaneously for 

1 second or longer.

The peak/bottom value can be reset, when displaying the peak value (bottom value).

To reset the peak/bottom value, press the 

and 

buttons simultaneously for 1 second

or longer.

Key lock function

To use each of these functions, refer to the operation manual from SMC website 

(URL http://www.smcworld.com) or contact SMC.

Maintenance

OUT2 over
current error

Accumulated

flow is displayed

(Flashing)

Accumulated

flow is displayed

(Flashing)

Accumulated
flow error

To change setting, refer to the operation manual from SMC website

(URL http://www.smcworld.com) or contact SMC.

[ inP] External input

3

[m id] 0.4 MPa minimum, 0.6 MPa maximum

[ on] Display ON

[

n] Normal output

1

2

3

1

2

Mounting screws

Screw is prepared by customer.

DIN rail is prepared by customer.

DIN rail is not suitable for port size F02 (G1/4).

Bracket (Mounting hole)

Joint screws

Mounting hole

Spring washers

Bracket (Tapped)

1

2

DIN rail mounting screws

DIN rail 

mounting

bracket

Safety Instructions

Mounting

•Never mount the product in a place where it will be used as a mechanical support.

•Mount the product so that the fluid flows in the direction indicated by the arrow on the side

of the body.

Safety Instructions

Summary of Product parts

Mounting and Installation

CAUTION indicates a hazard with a low level of risk which, if

not avoided, could result in minor or moderate injury.

Caution:
Warning:
Danger:

WARNING indicates a hazard with a medium level of risk

which, if not avoided, could result in death or serious injury.

DANGER indicates a hazard with a high level of risk which,

if not avoided, will result in death or serious injury.

Indicator LED

Displays the output status of OUT1 and OUT2.
When the accumulated pulse output mode is selected, the LED will turn OFF.
LED is ON when the output is ON.

LED display

Displays the flow, the status of setting mode and error indication. (2-colour display)

SET (S) button

The body of the product.

Body

Orifice mechanism to adjust the flow rate.

Flow adjustment valve

Name

Description

These safety instructions are intended to prevent hazardous situations and/or
equipment damage.
These instructions indicate the level of potential hazard with the labels of
"Caution", "Warning" or "Danger". They are all important notes for safety and must
be followed in addition to International standards (ISO/IEC) and other safety
regulations.

Do not operate the product outside of the specifications.

Do not use for flammable or harmful fluids.
Fire, malfunction or damage to the product can result.
Verify the specifications before use.

Do not disassemble, modify (including changing the printed circuit board) or repair.

An injury or failure can result.

Do not operate in an atmosphere containing flammable, explosive or corrosive gas.

Fire, explosionor corrosion can result.
This product is not designed to be explosion proof.

Do not use the product in a place where static electricity is a problem.

Otherwise it can cause failure or malfunction of the system.

If using the product in an interlocking circuit:

•Provide a double interlocking system, for example a mechanical system
•Check the product regularly for proper operation
Otherwise malfunction can result, causing an accident.

The following instructions must be followed during maintenance:

•Turn off the power supply
•Stop the air supply, exhaust the residual pressure and verify that the air is released before performing

maintenance work

Otherwise an injury can result.

After maintenance is complete, perform appropriate functional inspections and leak tests.

Stop operation if the equipment does not function properly or there is a leakage of fluid.
When leakage occurs from parts other than the piping, the product might be faulty.
Disconnect the power supply and stop the fluid supply.
Do not apply fluid under leaking conditions.
Safety cannot be assured in the case of unexpected malfunction.

Do not touch the terminals and connectors while the power is on.

Otherwise electric shock, malfunction or damage to the product can result.

Warning

Caution

Do not use the product for flammable fluid.

Fire or explosion can result.
Only air, N

2

, are applicable.

Used to lock the flow adjustment valve.

Lock ring

Used to mount the product on a DIN rail or directly to a panel.

Through hole

Panel

Insert

1

2

Bracket

Installation

Panel mounting (Only PFMB7201)

•Refer to the diagram and table below for mounting details.

•Refer to the dimension from SMC website (URL http://www.smcworld.com) for panel

thickness and panel mount cut-out dimensions.

Lead wire for power supply and outputs.

Lead wire with connector

Operator

The operation manual is intended for those who have knowledge of machinery
using pneumatic equipment, and have sufficient knowledge of assembly,
operation and maintenance of such equipment. Only those persons are
allowed to perform assembly, operation and maintenance.
Read and understand the operation manual carefully before assembling,
operating or providing maintenance to the product.

Body

Symbol

A

B

C

D

E

F

G

H

Display

Name

Description

Connector

Piping port

See below.

Connector for electrical connections.

PFMB7201

PFMB7501/7102/7202

A

H

G

D

E

B

C

D

F

IN

IN

OUT

A

B

E

C

D

D

IN

OUT

Display

Symbol

I

J

K

L

M

N

UP (

) button

DOWN (

) button

Press this button to change the mode and to set a value.

Selects the mode and decreases the ON/OFF set value.

Unit display

PFMB7201

PFMB7501/7102/7202

K
M

L

I

J

K
L
M

I

J

N

S

S

O

For piping connections. Connected to the fluid inlet at IN and to the fluid outlet at
OUT.

Bracket mounting

•Refer to the diagram and table below for mounting details.

•Refer to the dimension from SMC website (URL http://www.smcworld.com) for bracket

thickness and mounting hole dimensions.

Model

PFMB7201

Accessory

0.45 to 0.55 Nm

PFMB7501

M3 screws (4 pcs.)

PFMB7102

Mounting bracket

Mounting screws

Tightening torque

Mounting to equipment

Screw

M4 screws (4 pcs.)

Model

PFMB7201

Joint screws

0.35 to 0.45 Nm

Bracket

Screw

Tightening torque

DIN rail mounting bracket

Screw

Tightening torque

DIN rail mounting screws

0.35 to 0.45 Nm

Model

PFMB7201

12 to 14 Nm

PFMB7501

28 to 30 Nm

Required torque

Model

PFMB7201

Nominal thread size

Rc1/4, NPT1/4

17 mm

G1/4

21 mm

PFMB7501

1/2

30 mm

Width across flats of attachment

Caution

Attachment

Caution

Attachment

Connecting/Disconnecting

•When mounting the connector, insert it straight into the socket, holding the lever and

connector body, and push the connector until the lever hooks into the housing, and locks.

•When removing the connector, press down the lever to release the hook from the

housing and pull the connector straight out.

Lever

Socket

Connector body

1

2

3

4

Brown

White

DC(+)

OUT2/Analogue output/External input

Black

Blue

OUT1

DC(-)

+  

2  

1  

-

1
2
3
4

The output will not operate for 3 seconds after supplying power.

The identification code of the product is displayed.

Power is supplied

Press the

S button for

2 seconds

or longer.

: The outputs will continue to operate during setting.

: If a button operation is not performed for 30 seconds during the setting, the display will flash.

(This is to prevent the setting from remaining incomplete if, for instance, an operator were to leave during setting)

: 3 step setting mode and Function selection mode are reflected on each other.

Flow Setting (set value only) of OUT1 · OUT2

Fl

ow

 [L

/m

in

]

Hysteresis

[H_1]

Switch ON

Switch OFF

Set value

[P_1]

Time [s]

Item

[H_1] Hysteresis of OUT1
[P_2] Set value of OUT2 

[H_2] Hysteresis of OUT2 

[P_1] Set value of OUT1

PFMB7201

10

100

10

100

Screw is prepared by customer.

Outline of settings

DIN rail mounting (Only PFMB7201)

•Refer to the diagram and table below for

mounting details.

Flow direction

OUT side

IN side

Restrictor

8 cm or longer

[Measurement mode]

Measurement mode is the condition where the flow is detected and displayed, and

the switch function is operating. This is the basic mode; other modes should be

selected for set-point changes and other function settings.

Flow setting

(3 step setting mode)

Function setting

(Function selection mode)

Other functions

Selects the mode and increases the ON/OFF set value.

Indicates the unit currently selected.

: The table lists the parts when a flow adjusting valve is included.

3 step setting mode

In this mode, only the set values can be input, in just 3 steps.

: Only available for models with switch outputs for both OUT1 and OUT2.

: When the reversed display is used, the function of the

and

buttons is reversed.

0.5 to 0.7 Nm

Piping

•Never mount the product upside down.

•The straight piping length shall be 8 cm or longer.

Otherwise, if a straight section of piping is not installed, the accuracy varies by

approximately 

±

2%F.S.

•Avoid sudden changes in the piping size on the IN side of the product.

•Do not release the OUT side piping port of the product directly to the atmosphere

without the piping connected.

If the product is used with the piping port released to atmosphere, the accuracy may vary.

Piping for the metal attachment

•Tighten to the specified torque. Refer to the table below for the required torque values.

•Use a suitable spanner for the appropriate torque. Do not use a spanner 40 cm or

longer.

•If the tightening torque is exceeded, the product can be broken.

If the tightening torque is insufficient, the fitting may become loose.

•Avoid any sealing tape getting inside the flow path.

•Ensure there is no leakage after piping.

•When mounting the fitting, a spanner should be used on the metal part (attachment) of

the fitting only.

Holding other parts of the product with a spanner may damage the product.

Specifically, make sure that the spanner does not damage the connector.

Direct mounting

•Refer to the diagram and table below for mounting details.

•Refer to the dimension from SMC website (URL http://www.smcworld.com) for mounting

hole size.

Thank you for purchasing an SMC PFMB7 series Digital Flow Switch.
Please read this manual carefully before operating the product and make sure you
understand its capabilities and limitations. Please keep this manual handy for
future reference.

To obtain the operation manual about this product and

control unit, please refer to the SMC website

(URL http://www.smcworld.com) or contact SMC directly.

Before Use

Digital Flow Switch

PFMB7201/7501/7102/7202

PFMB7102

Model

PFMB7201

Self tapping screws

Nominal size:

3.0 x 4 pcs.

0.5 to 0.7 Nm

PFMB7501

PFMB7102

Direct mounting

M3 screws (2 pcs.)

0.35 to 0.45 Nm

Screw

Tightening torque

Model

Direct mounting

Screw

Tightening torque

PFMB7102

PFMB7102

PFMB7202

PFMB7102

PFMB7202

3/4

35 mm

Connector pin numbers (lead wire)

PFMB7501

25

250

25

250

PFMB7102

50

500

50

500

PFMB7202

100

1000

100

1000

[L/min]

Press the

button continuously

to keep decreasing the set value.

[ 250] 250 L/min (PFMB7501)

[ 500] 500 L/min (PFMB7102)

[1000] 1000 L/min (PFMB7202)

[ 25] 25 L/min (PFMB7501)

[ 50] 50 L/min (PFMB7102)

[ 100] 100 L/min (PFMB7202)

[ 100] 100 L/min (PFMB7201)

[ 10] 10 L/min (PFMB7201)

[ 250] 250 L/min (PFMB7501)

[ 500] 500 L/min (PFMB7102)

[1000] 1000 L/min (PFMB7202)

[ 25] 25 L/min (PFMB7501)

[ 50] 50 L/min (PFMB7102)

[ 100] 100 L/min (PFMB7202)

PF

※※

-OMP0003-A

How to reset the product after a power cut or when the power has been

unexpectedly removed

The settings of the product are retained from before the power cut or 

de-energizing.

The output condition also recovers to that before power cut or de-energizing, but

may change depending on the operating environment. Therefore, check the safety

of the whole installation before operating the product.

Default settings

The default settings are shown below.

When the flow exceeds the set value [P_1], the switch will be turned ON.

When the flow falls below the set value by the amount of hysteresis [H_1] or more, the

switch will turn OFF.

If the operation shown in the diagram below is acceptable, then keep these settings.

For more detailed settings, set each function in the function selection mode.

O

Reference condition
indicator

Indicates the reference condition selected. LED is ON (red) when standard
condition is selected.

(

)

Connector pin numbers

Wire colour

Description

Press the

S button

once.

Default settings

Wiring

Connection

•Connections should only be made with the power supply turned off.

•Use a separate route for the product wiring and any power or high voltage wiring.

Otherwise, malfunction may result due to noise.

•Ensure that the FG terminal is connected to ground when using a commercially

available switch-mode power supply. When a switch-mode power supply is connected

to the product, switching noise will be superimposed and the product specification can

no longer be met. This can be prevented by inserting a noise filter, such as a line noise

filter and ferrite core, between the switch-mode power supply and the product or by

using a series power supply instead of a switch-mode power supply.

Error indication

NOTE

The direct current power supply used should be UL approved as follows.

Circuit (class 2) of maximum 30 Vrms (42.4 V peak) or less, with UL 1310
class 2 power supply unit or UL 1585 class 2 transformer.

The product is a UL approved product only if it has a 

mark on the body.

Function selection mode

In measurement mode, press the S button for 2 seconds or longer, to display [F 0].

The [F

] indicates the mode for changing each Function Setting.

Press the S button for 2 seconds or longer in function selection mode to return to

measurement mode.

Reviews: