Digital Flow Switch

Operation Manual

PF2A7

H

Installation

•Never mount the product in a location that will be used as a foothold.
•The rotation angle of the monitor is 270

o

, in steps of 90

o

. Rotating the display

part with excessive force will damage the end stop.

Piping port

(IN side)

Connector

Body

Monitor part

Piping port

(OUT side)

Lead wire and connector

Item

Body

Description

Monitor part

See below.

Piping port

Connected to the fluid inlet at IN side and to the fluid outlet at OUT side.

Body

The body of the product.

Connector

Connector for electrical connections.

Lead wire and connector

Lead wire to supply power and transmit output signals.

LCD display

Indicator LED (flow rate)

Indicator LED (reference condition)

Indicator LED (output)

button (MODE)

FLOW SWITCH

button (DOWN)

button (UP)

ANR

OUT

Unit display

button (SET)

ft

3

x10

6

ft

3

x10

3

m

3

x10

3

m

3

ft

3

L/min L

CFM

U P

DOWN

MODE

SET

Item

Monitor part

Description

LCD display

Displays the flow value, setting mode, and error indication.

Indicator LED (reference condition)

Indicates the reference condition selected. LED is ON (Red) when standard
condition is selected.

Indicator LED (output)

Indicates the output status of OUT1. LED is ON (Red) when OUT1 is ON.
The LED flashes when an over current error occurs.

button (UP)

Selects the mode or increases the ON/OFF Set value.

button (SET)

Press this button to change to another mode and to set a value.

button (MODE)

Moves on to the function selection mode.

button (DOWN)

Selects the mode or decreases the ON/OFF Set value.

Connector pin numbers

(On the product)

1

3

2

4

1

DC(+)

2

Analogue output

3

DC(-)

4

OUT1

Thank you for purchasing an SMC PF2A7

H Series Digital Flow Switch.

Please read this manual carefully before operating the product and make sure you
understand its capabilities and limitations.
Please keep this manual handy for future reference.

To obtain more detailed information about operating this product, please
refer to the SMC website (URL http://www.smcworld.com) or contact SMC
directly.

Safety Instructions

These safety instructions are intended to prevent hazardous situations and/or
equipment damage.
These instructions indicate the level of potential hazard with the labels of
"Caution", "Warning" or "Danger". They are all important notes for safety and must
be followed in addition to International standards (ISO/IEC) and other safety
regulations.

CAUTION indicates a hazard with a low level of risk
which, if not avoided, could result in minor or
moderate injury.

Operator

This operation manual is intended for those who have knowledge of machinery
using pneumatic equipment, and have sufficient knowledge of assembly,
operation and maintenance of such equipment. Only those persons are
allowed to perform assembly, operation and maintenance.
Read and understand this operation manual carefully before assembling,
operating or providing maintenance to the product.

Caution:

Warning:

Danger:

WARNING indicates a hazard with a medium level of
risk which, if not avoided, could result in death or
serious injury.

DANGER indicates a hazard with a high level of risk
which, if not avoided, will result in death or serious
injury.

Safety Instructions

Do not disassemble, modify (including changing the printed circuit board) or repair.

An injury or failure can result.

Do not operate in an atmosphere containing flammable, explosive or corrosive gas.

Fire or an explosion can result.
This product is not designed to be explosion proof.

Do not use the product for flammable fluid.

A fire or explosion can result.

Do not use the product in a place where static electricity is a problem.

Otherwise it can cause failure or malfunction of the system.

If using the product in an interlocking circuit:
•Provide a double interlocking system, for example a mechanical system
•Check the product regularly for proper operation

Otherwise malfunction can result, causing an accident.

The following instructions must be followed during maintenance:
•Turn off the power supply
•Stop the air supply, exhaust the residual pressure and verify that the air is released before performing

maintenance work

Otherwise an injury can result.

After maintenance is complete, perform appropriate functional inspections and leak tests.

Stop operation if the equipment does not function properly or there is a leakage of fluid.
When leakage occurs from parts other than the piping, the product might be faulty.
Disconnect the power supply and stop the fluid supply.
Do not apply fluid under leaking conditions.
Safety cannot be assured in the case of unexpected malfunction.

Do not touch the terminals and connectors while the power is on.

Otherwise electric shock, malfunction or damage to the product can result.

Do not operate the product outside of the specifications.

Do not use for flammable or harmful fluids.
Fire, malfunction, or damage to the product can result.
Verify the specifications before use.

Warning

Caution

Maintenance

How to reset the product after a power cut or forcible de-energizing

The setting of the product will be retained as it was before a power cut or 
de-energizing.
The output condition is also basically recovered to that before a power cut or
de-energizing, but may change depending on the operating environment.
Therefore, check the safety of the whole installation before operating the product.

Summary of Product parts

Mounting and Installation

Indicator LED (flow rate)

Flashes with the cycle proportional to the flow rate.

Unit display

Display the selected unit.

IN side

OUT side

FLOW SW

ITCH

End stop

position

End stop

position

90°

180°

270°

Connecting the piping

•Ensure that the metal piping attachments are tightened to the required torque

(refer to the table below).

•If the tightening torque is exceeded, the product can be broken. If the

tightening torque is insufficient, the fittings may become loose.

•When connecting piping to the product, a spanner should be used on the

metal piping attachment only. Using a spanner on other parts may damage
the product.

•Avoid any sealing tape from entering inside the piping.
•Ensure that there is no leakage from loose piping.


 

Dis

pla

y in

sta

nta

ne

ou

s fl

ow

 

 D

isp

lay

 ac

cu

m

ula

ted

 flo

+

3 sec. or longer

Input of the Set point

Instantaneous output mode

Accumulated output mode

Press

and

Press

and

6 sec. or longer

1: Operate only the product with unit selction function (Model indication: without M).

2: A set of value is not input, when accumulate pulse output mode.

3: Depend on the setting of switch operation in initialize mode.

4: Displayed in turn.

5: Setting is available when Set point 1 < Set point 2.

2

Accumulated value is reset

Display

instantaneous flow

The display digit of the

accumulate flow rate is set.

Unit flashes.

 m

3

 

 m

3

×10

3

 

 L ...

Set value

or      

3

4

Set value (lower digits)

Input of the Set point 2

or      

3

4

Set value

or      

3

4

Set value

Set value (middle digits)

Input of hysteresis  

5

Set value

or      

3

4

Set value (upper digits)

3 sec. or longer

Display

accumulated flow

The display digit of the accumulate flow

rate is changed.  L 

 m

3

 

 m

3

×10

3

 

 L ...

Function selection mode

/

Output mode

Instantaneous

output mode

Accumulated

output mode

Accumulated pulse

output mode

/

/

/

/

Initialize mode
Items below can be set one by one.

1.Display mode          2.Unit selection function  

1

3.Output mode           4.Input of Set point

5.Switch operation     6.Key-lock function

Display mode

Display

instantaneous flow

Display

accumulated flow

Unit selection function  

1

L/min, L

CFM, ft

3

Reset to the default setting

Key-lock function

Unlock

Lock

Switch operation

Reverse output

Non-Reverse output

Reference condition

Standard condition

Normal condition

Accumulated value hold

Not held

Held

ANR

OUT

ft

3

x10

6

ft

3

x10

3

m

3

x10

3

m

3

m

3

ft

3

L/min L

CFM

ANR

OUT

ft

3

x10

6

ft

3

x10

3

m

3

x10

3

m

3

m

3

ft

3

L/min L

CFM

Measurement mode

(Accumulated flow)

: Accumulation starts as the power supply starts.

/

/

/

/

/

: Start the setting here to supply power under the default settings.

Measurement mode

(Instantaneous flow)

m

3

×10

3

m

3

L

Set value

4

4

Set value

or      

3

Input of the Set point 1

List of outputs

Find the diagram of the output required in the table below. Perform settings
following the Set value column on the right.

In

s

ta

n

ta

n

e

o

u

s

 f

lo

w

Switch output diagram

Output mode

Switch operation

Set value

Instantaneous

output mode

Non-Reverse

output

Set point 2     Set point 1

Hysteresis mode

2

Set point 1     Set point 2

Window comparator mode

Set point 1

Set point 2

Window comparator mode

Reverse output

OFF

ON

Hysteresis

P_2 P_1

Instantaneous flow

OFF

ON

Hysteresis 

1

Hysteresis 

1

P_1

P_2 Instantaneous flow

OFF

ON

Hysteresis

n_2 n_1

Instantaneous flow

OFF

ON

Hysteresis 

1

Hysteresis 

1

n_1

n_2 Instantaneous flow

Set point 2     Set point 1

Hysteresis mode

2

Wiring

•Connections should only be made with the power supply turned off.
•Use separate routes for the product wiring and any power or high voltage

wiring. Otherwise, malfunction may result due to noise.

•Ensure that the FG terminal is connected to ground when using a commercially

available switch-mode power supply. When a switch-mode power supply is
connected to the product, switching noise will be superimposed and the
product specification can no longer be met. This can be prevented by inserting
a noise filter, such as a line noise filter and ferrite core, between the switch-
mode power supply and the product, or by using a series power supply instead
of a switch-mode power supply.

Connecting the wiring

•Align the lead wire connector with the connector key groove, and insert

vertically.

•Connection is complete when the knurled part is fully tightened. Check that

the connection is not loose.

Connector Pin numbers

When the lead wire with connector designated for the PF2A7 is used, the wire
colours will apply as shown in the diagram.

1

4

2

3

Power is supplied

Outline of setting

Pin number

Content

2

Analogue output

3

DC(-)

4

OUT1

The output will not operate for 3 seconds after supplying power.

The identification code of the product is displayed.

Measurement mode

The mode in which the flow is detected and displayed, and the switch output
is operating.
This is the basic operating mode; and other modes should be selected for
setting changes and other function settings.

Accumulated flow can be displayed up to 9999999999 L (999999999.9 ft

3

).

The LCD display displays up to 5 digits at one time. The display is divided
into three parts (upper digits, middle digits and lower digits).

Function selection mode

Other functions

button

1

DC(+)

Colour

White

Blue

Black

Brown

Setting flow chart

A

c

c

u

m

u

la

te

d

 f

lo

w

Accumulated
output mode

Non-Reverse

output

Reverse output

OFF

ON

Time

Time

Accumlated flow

P_3

OFF

ON

Time

Time

Accumlated flow

n_3

A

c

c

u

m

u

la

te

d

 p

u

ls

e

Accumulated

pulse output

mode

No Set value input

No Set value input

Reverse output

OFF

ON

Time

50 ms

OFF

ON

Time

50 ms

Error indication

: If the error cannot be reset after the above measures are taken, then please contact SMC.

Function selection mode

Default settings

The default settings are as follows.
If this condition is acceptable, then keep these settings.

In measurement mode, press the 

button , to display [F_0].

This [F_ ] indicates the mode for changing each functional setting.

Specifications / Outline with Dimensions

Refer to the product catalogue or SMC website (URL http://www.smcworld.com) for
more information about the product specifications and outline dimensions.

Note: Specifications are subject to change without prior notice and any obligation on the part of the manufacturer.
© 2011 SMC Corporation All Rights Reserved

Akihabara UDX 15F, 4-14-1, Sotokanda, Chiyoda-ku, Tokyo 101-0021, JAPAN
Phone: +81 3-5207-8249   Fax: +81 3-5298-5362

URL http://www.smcworld.com

Troubleshooting

Non-Reverse

output

Refer to the SMC website (URL http://www.smcworld.com) for more information
about troubleshooting.

1: Hysteresis can be set between "0" and "3% of maximum rated flow". If the difference between Set point 1 and

Set point 2 is less than "6% of maximum rated flow", the maximum Set value of hysteresis is (Set point 1 -
Set point 2) divided by 2.

2: When Set point 1 = Set point 2, chattering may occur. 

Display unit

Maximum flow

display value

L display

[   U_1]

9999999999 L

ft display

[   U_2]

999999999.9 ft

3

Display digit

9999 m

3

×10

3

(9999

L)

99999 m

3

(99999

L)

999 ft

3

×10

6

(999

.

ft

3

)

99999 ft

3

×10

3

(99999

.

ft

3

)

Upper digits

Middle digits

99999 L

9999.9 ft

3

Lower digits

: Operate only the product with unit selection function.

[F_0]

Selection of display mode

Item

Unit selection function     

1

Selection of output mode

Input of Set point 1

[F_1]

Selection of display mode

[F_3]

Selection of output mode

Input of Set point 1

1: Operate only the product with unit selection function.

2: Setting is available when Set point 1 

Set point 2.

Not displayed when Set point 1

Set point 2.

[    d_1] Display instantaneous flow

Default Setting

[    U_1] L/min

[oU1_0] Instantaneous output mode

50% of max. rated flow

[     d_1] Display instantaneous flow

[oU1_0] Instantaneous output mode

50% of max. rated flow

Input of Set point 2

Input of hysteresis     

2

50% of max. rated flow

[         0]

Input of Set point 2

Input of hysteresis     

2

Selection of switch operation

Key-lock function

50% of max. rated flow

[         0]

[oU1_n] Reverse output

[    UnL] Unlocked

[F_2]

Unit selection function     

1

[    U_1] L/min

[F_4]

Selection of switch operation

[F_6]

Input of Set point 1

Input of Set point 2

[oU1_n] Reverse output

50% of max. rated flow

50% of max. rated flow

Input of hysteresis     

2

[         0]

[F_5]

Key-lock function

[    UnL] Unlocked

[F_7]

Selection of reference condition

[     Anr] Standard condition

[F_8]

Accumulated value hold

[    oFF] Not held

To set each of these functions, refer to the SMC website
(URL http://www.smcworld.com) for more information about other functions in
detail.

Other functions

Reset of the accumulated flow
Reset to the default setting

Flow has exceeded the upper
limit of the display flow range.

Reduce the flow.

Display

Type

Troubleshooting

The switch output load
current is more than 80 mA
(OUT1).

Turn the power off and remove
the cause of the over current.
Then turn the power on again.

The set data has been
changed unexpectedly.

Exceeds the range of the
2nd. turn of flow indication.

To reset, press the 

button for

6 seconds or longer while the 
button is pressed. Then set all
data again.

Stop using and please contact
SMC.

The internal circuit could be
damaged.

To reset the accumulated flow
value, press the 

button for 

6 seconds or longer while the 
button is pressed.

Excessive
instantaneous
flow

Error Name

Over current
error

System error

Excessive
accumulated
flow

Upper digits

Middle digits

Lower digits

Upper digits

Middle digits

Lower digits

(When [    U_1] is selected)

(When [    U_2] is selected)

Accumulated flow displayed

(flashing)

ANR

OUT

ft

3

x10

6

ft

3

x10

3

m

3

x10

3

m

3

ft

3

L/min L

CFM

ANR

OUT

ft

3

x10

6

ft

3

x10

3

m

3

x10

3

m

3

ft

3

L/min L

CFM

Piping

•Use the product within the specified operating pressure range and temperature

range.

•Proof pressure is 2.25 MPa.
•Connect the piping to the fittings.
•Mount the product so that the fluid direction is the same as the arrow indicated

on the product.

•Never mount the product upside down.
•The piping on the IN side must have a straight section of piping whose length

is 8 times the piping diameter or more.

•Avoid sudden changes in the piping size on the IN side of the product.

Metal piping attachment

Knurled part

Flow direction

OUT side

IN side

Restrictor

D x 8 times

Port size D

FLOW SWITCH

Model

Width across flats

of attachment

PF2A706H

PF2A712H

65 mm

PF2A703H

55 mm

75 mm

Rc(NPT)1

1

/

2

Rc(NPT)2

Rc(NPT)1

Nominal

thread size

Tightening torque

48 to 50 Nm

36 to 38 Nm