Lochinvar ProtoNode Start-up Guide
Page 51 of 56
Gas Pressure Switch 1
BI
5
DI
5
Louver Proving Switch 1
BI
6
DI
6
Air Pressure Switch/Flap Vlv 1
BI
7
DI
7
Blocked Drain Switch 1
BI
8
DI
8
Auto Reset High Limit 1
BI
9
DI
9
Flame 1
BI
10
DI
10
Enable/Room Thermostat 1/Stg 1
BI
11
DI
11
Tank Thermostat
BI
12
DI
12
Run-time Contacts
BI
13
DI
13
Alarm Contacts 1
BI
14
DI
14
CH Pump 1
BI
15
DI
15
DHW Pump 1
BI
16
DI
16
Gas Vlv 1
BI
17
DI
17
System Pump
BI
18
DI
18
Mains Fan 1
BI
19
DI
19
External Spark
BI
20
DI
20
Discrete Inputs 1 - 16
AI
21
AI
21
Discrete Inputs 17 - 32
AI
22
AI
22
Discrete Inputs 33 - 48
AI
23
AI
23
System/Cascade Setpoint
AI
24
AI
24
Cascade Total Power
AI
25
AI
25
Cascade Current Power
AI
26
AI
26
Outlet Setpoint 1
AI
27
AI
27
Outlet Temperature 1
AI
28
AI
28
Inlet Temperature 1
AI
29
AI
29
Flue Temperature 1
AI
30
AI
30
Firing Rate 1
AI
31
AI
31
Boiler 1 Status Code
AI
32
AI
32
Boiler 1 Blocking Code
AI
33
AI
33
Boiler 1 Lockout Code
AI
34
AI
34
Discrete Inputs 49-64
AI
35
AI
35
Configuration
AV
36
AO
36
Coils
AV
37
AO
37
0-10 Volt Input/Rate Cmd/SP Cmd
AV
38
AO
38
Tank Setpoint
AV
39
AO
39
Tank Temperature
AV
40
AO
40
Outdoor Temperature
AV
41
AO
41
System Supply Temperature
AV
42
AO
42
System Return Temperature
AV
43
AO
43
Appendix C.6 Knight FTXL Modbus RTU Mappings to BACnet and Metasys N2
Point Name
BACnet
Object Type
BACnet
Object ID
N2 Data
Type
N2
Address
Room Thermostat 1
BV
1
DO
1
Room Thermostat 2
BV
2
DO
2
Room Thermostat 3
BV
3
DO
3
Tank Thermostat
BV
4
DO
4
Flow Switch
BI
5
DI
5
Gas Pressure Switch
BI
6
DI
6
Louver Proving Switch
BI
7
DI
7
Air Pressure Switch
BI
8
DI
8
Blocked Drain Switch
BI
9
DI
9
Auto Reset High Limit
BI
10
DI
10
Flame
BI
11
DI
11
Room Thermostat 1
BI
12
DI
12
Tank Thermostat
BI
13
DI
13
Room Thermostat 2
BI
14
DI
14
Run-time Contacts
BI
15
DI
15
Alarm Contacts
BI
16
DI
16
CH Pump
BI
17
DI
17
DHW Pump 1
BI
18
DI
18
Louver Relay
BI
19
DI
19
Gas Valve
BI
20
DI
20