- 28 -
No.JXC
※
-OMV0005-A
10. Memory map
10.1 Process data
10.1.1
Process data input (from JXCL1 controller to IO-Link master)
(1) Process data input list
Byte No.
Signal name
Description
Unit
0,1
Controller status flag
Flag to indicate the controller (actuator) status
-
2-5
Position
Current actuator position
0.01mm
6,7
Speed
Current actuator speed.
mm/s
8,9
Pushing F
Current actuator pushing force
%
10-13
Target Pos
Target position of the actuator
0.01mm
(2) Process data input details
● Byte 0,1h: Controller status signal
Byte No.
Bit
Signal name
Description
0
0
OUT0
When the operation is started and “DRIVE” is turned OFF,
the step No. executed by “DRIVE” will be refreshed/updated
by the combination of “OUT0” to “OUT5” (binary digit).
(E.g.) Step data No.3 is output
OUT5
OUT 4 OUT 3 OUT 2 OUT 1 OUT 0
OFF
OFF
OFF
OFF
ON
ON
Caution
(1) When
“RESET” is turned ON, these signals turn OFF.
(2) During the alarm, these signals output the alarm group.
(3) During the pushing operation, if the actuator runs over
the defined pushing width, these signals turn OFF.
1
OUT1
2
OUT2
3
OUT3
4
OUT4
5
OUT5
6
INIT
After C24V power is supplied, this signal turns on when there
are no problems with the controller and the motor drive circuit
is ready to operate.
Once this signal is ON, it does not turned off until the power
supply is disconnected.
7
-
-
1
8
BUSY
This terminal is ON during the movement of the actuator
(during the positioning operation, etc.).
Caution
During the pushing operation without movement (no
movement but the actuator generating the pushing force),
“BUSY” is OFF.
9
SVRE
When the servo motor is OFF, “SVRE” is OFF. When the
servo motor is ON, “SVRE” is ON.
10
SETON
When the actuator is in the SETON status (the position
information is established), this signal turns ON.
When the position status is not established, this signal is OFF.