background image

Installation and Maintenance Manual
Series ITV20*0-X155, ITV30*0-X37 
(DeviceNet Compatible Type). 

 Electro-Pneumatic Regulator

For future reference, please keep this manual in a safe place

This manual should be read in conjunction with the current catalogue 

From SMC Japan Document No. ITV2-0M00034

 

These safety instructions are intended to prevent a hazardous
situation and / or equipment damage. These instructions indicate
the level of potential hazard by label of “Caution” “Warning”, or
“Danger”. To ensure safety, be sure to observe ISO 4414 

(Note 1)

, JIS

B 8370 

(Note 2)

 and other safety practices.

(Note1): ISO 4414: Pneumatic fluid power-Recommendations for
the application of equipment to transmission and control systems.
(Note 2): JIS B 8370: Pneumatic system axiom

CAUTION

: Operator error could result in injury or equip-

ment damage. 

WARNING

: Operator error could result in serious injury

or loss of life. 

DANGER

: In extreme conditions, there is a possible result

of serious injury or loss of life. 

1.

The compatibility of pneumatic equipment is the
responsibility of the person who designs the
pneumatic system or decides its specifications.

Since the products specified here are used in various
operating conditions, their compatibility for the specific
pneumatic system must be based on specifications or after
analysis and/or tests to meet your specific requirements.

2.

Only trained personnel should operate
pneumatically operated machinery and equipment.

Compressed air can be dangerous if an operator is unfamiliar
with it. Assembly, handling or repair of pneumatic systems
should be performed by trained and experienced operators.  

3.

Do not service machinery / equipment or attempt to
remove component until safety is confirmed.

1) Inspection and maintenance of machinery / equipment

should only be performed after confirmation of safe
locked-out control positions.

2) When equipment is to be removed, confirm the safety

process as mentioned above. Switch off air and electrical
supplies and exhaust all residual compressed air in the
system.

3) Before machinery / equipment is re-started, ensure all

safety measures to prevent sudden movement of
cylinders etc. (Supply air into the system gradually to
create back-pressure, i.e. incorporate a soft-start valve.)

4.

Contact SMC if the product is to be used in any of
the following conditions:

1) Conditions and environments beyond the given

specifications, or if product is used outdoors.

2) Installation on equipment in conjunction with atomic

energy, railway, air navigation, vehicles, medical
equipment, food and beverage, recreation equipment,
emergency stop circuits, press applications, or safety
equipment.

3) An application which has the possibility of having

negative effects on people, property, or animals requiring
special safety analysis.

Ensure that the air supply system is filtered to 5 micron   

  

(Note 1)

Excludes current consumption of DeviceNet communication line.

(Note 2)

Select Set pressure with 4096 resolution, corresponding to the maximum setting pressure of 100%

(Note 3)

Select monitor pressure with 4096 resolution, corresponding to the maximum output pressure of 100%

Fig 3  

When the input signal increases, the supply solenoid valve 

���

 turns on and the exhaust solenoid valve 

���

 turns off. Supply pressure is

passed to the pilot valve 

���

 through the supply solenoid valve. The pilot valve will open the main valve allowing partial supply pressure to

pass to the out port.

The pressure sensor 

���

 will provide output pressure feedback to the control circuit 

���

. The control circuit will balance the input signal and

output pressure to ensure that the output pressure remains proportional to the input signal. 

Safety Instructions

WARNING

CAUTION

Specifications

Model

ITV2010-X155

ITV2030 - X155

ITV2050-X155

ITV3010-X37

ITV3030 - X37

ITV3050-X37

Min.Supply Pressure

Setting Pr 0.1 MPa

Max.Supply Pressure

0.2 MPa (2.0 kgf/cm

2

)

1.0 MPa (10.2 kgf/cm

2

)

Setting Pressure Range

0.005-0.1MPa

0.005-0.5MPa

0.005-0.9MPa

Max. Flow Rate

1500 l/ min (ANR) ITV20** (SUP: at 0.7 MPa)
5000 l/ min (ANR) ITV30** (SUP: at 0.7 MPa)

Supply Voltage

24 VDC 10%

Current Consumption

Max. 012A

Note 1

Input Signal

Indicates Input Signal by 12 bit 

Note 2

Output Signal

Retransmits Output Pressure by 12 bit 

Note 3

Linearity

1% or less (Full Scale)

Hysteresis

0.5% or less (Full Scale)

Repeatability

0.5% or less (Full Scale)

Sensitivity

0.2% or less (Full Scale)

Temperature Characteristics

0.12% or less (Full Scale) /

Protection Structure

Main unit: IP65, Cable connector: IP67

Ambient and fluid temperature

0-50

 (without condensation)

±

±

±

±

°

C

°

C

Operation Principle

             

Fig 1

Fig 2

Fig 4

Symbol

Power supply

Input signal

Pilot valve

Supply
solenoid valve

SUP

EXH

Control
circuit

Pressure
indicator

Exhaust
solenoid valve

Pilot EXH

Pressure
sensor

OUT

  

Fig 5

 

Connect the cables to the connectors on the unit as shown in the
following diagrams. Take precautions as incorrect wiring will
damage the unit. Use a DC power supply capable of supplying the
necessary power requirements with minimal ripple.

When 3m straight cable connection is specified, this refers to the
power supply cable, the communications cable should be ordered
separately.

Fig 6

Fig 7

Fig 8

   

  

Fig 9

 

Fig 10

Note:

Dip switch 9 is selected to temporarily hold or clear the
output pressure, in the event that either of the following
occur 

1.

When the DeviceNet line causes a communication error due
to disconnection.

Block line chart

Pressure sensor

Exhaust solenoid
valve

Pilot valve

Output
pressure

Control
circuit

Input signal

Supply solenoid
valve

Supply pressure

CAUTION

Wiring

Power Supply Line   

Address Switch

SUP

OUT

Communication
Line

Brown
White
Blue
Black

Supply Voltage
No Connect
GND
No Connect

Brown
White
Blue
Black

DeviceNet connections

No.

Code

Color

Function

1

Drain

Naked

Device shield for signal line

2

V+

Red

Power supply (+) to communication satation

3

V-

Black

Power supply (-) to communication satation

4

CAN-H

White

Device Net signal

5

CAN-L

Blue

Device  Net  signal

Protocol

DeviceNet Ver 2.0

Comm Speed

125 k, 250 k, 500 k BPS

Slave type

Group 2 only

Device type

00h (Generic Device)

Connections 
supported

Explicit, Polled I/O

Protocol

LED Display

PowerLED 

MOD/NET LED (Combined Module/Network Status)  

OFF

Power OFF (interface unit)

GREEN

Power ON (interface unit)

OFF

The unit is not on-line

FLASHING GREEN

The unit is on-line but not allocated

SOLID GREEN

The unit is on-line and allocated to a master

FLASHING RED

Recoverable fault, the I/o connection has timed out

SOLID RED

Unrecoverable fault, can not recover

POWER LED

MOD/NET LED

Address Dip Switch

Node address (6 bit) + Data rate (2 bit)

Date rate

Setting method

0-Dominated by switch, cannot 
overwrite with software (HW 
setting)

1-Dominated by software, 
Switches from 1 to 8 have no 
function (SW setting) 

Note:

For the communication error

0- Clear output pressure

1- Hold output pressure

2.

When the power supply to the ITV is switched off or
disconnected whilst unit is communicating. 

The condition of the output pressure during recovery of either
connection depends on the position of the dip switch.

0

Output pressure is Cleared

1

Output pressure is Held

1.

The setting of an address switch requires the removal of 4
screws in the front panel of the unit (Fig 6). Take care that the
panel hinges to 90 degrees maximum.

2.

After setting an address, always close and fix the panel
securely. Tighten the screws to a torque of 0.6 – 1.0 Nm.

 

1.

If the air pressure fails with power ‘on’ the solenoid will
‘flutter’. Turn off the power to stop the pressure supply or
make an input signal of 0%

1.

This product is pre-set at the factory and must not be
dismantled by the user. Contact your local SMC office for
advice.

2.

Ensure, when installing this product, that it is kept clear of
power lines to avoid noise interference.

3.

Ensure that load surge protection is fitted when inductive
loads are present (i.e. solenoid, relay etc.).

4.

Ensure precautions are in place if the product is used in a
‘free flow output’ condition. All will continue to flow
continuously.

5.

Do not use a lubricator on the input side of this product. If
lubrication is necessary, place the lubricator on the ‘output’
side.

6.

Ensure all air is exhausted form the product before
maintenance.

When you enquire about the product, please contact the following

SMC Corporation

Phone

Phone

AUSTRIA

(43) 2262-62 280

ITALY

(39) 02-92711

BELGIUM

(32) 3-355 1464

NETHER-
LANDS

(31) 20-531 8888

CZECH REP.

(420) 5-414 24611

NORWAY

(47) 67 12 90 20

DENMARK

(45) 70 25 29 00

POLAND

(48) 22-548 50 85

FINLAND

(358) 9-859 580

PORTUGAL

(351) 2-610 89 22

FRANCE

(33) 1-64 76 1000

SPAIN

(34) 945-18 4100

GERMANY

(49) 6103 4020

SWEDEN

(46) 8-603 0700

GREECE

(30) 1-342 6076

SWITZERLAND

(41) 52- 396 3131

HUNGARY

(36) 1-371 1343

TURKEY

(90) 212 221 1512

IRELAND

(353) 1-403 9000

UK

(44) 1908-56 3888

CAUTION

CAUTION

CAUTION

ITV2-TFI21GB