DJUSTING THE 

M

INIMUM 

A

ND 

M

AXIMUM 

P

RESSURES

The ITV allows the user to customize the minimum pressure (zero point) at 0% input

signal and the maximum pressure (span) at 100% input signal. The minimum pressure can be set
as low as 0% and as high as 50% of the full span. The maximum pressure can be set as low as
10% and as high as 100% of the full span.

For example, an ITV203 could be set to output 35 PSI at 0% input signal, and 43 PSI at

100% input signal (there must be at least 8 PSI separation). Similarly, the same ITV203 could be
set to output 0 PSI at 0% input signal, and 8 PSI at 100% input signal.

minimum pressure (zero) adjust

maximum pressure (span) adjust

M

ONITOR 

O

UTPUT

The ITV is available with one of three different monitor output signals:

 

ANALOG (ITV20

- 1):  Linear analog pressure monitor signal (1~5VDC).

 

Input impedance:

100K

 or greater

 

NPN DIGITAL (ITV20

- 2):  NPN open-collector output. Maximum load current:  30mA

 

PNP DIGITAL (ITV20

- 3):  PNP open-collector output. Maximum load current:  30mA

The NPN and PNP digital monitor outputs can be set to function in one of three different ways:

comparator mode

hysteresis mode

self-diagnostic mode

when P1<P2

when P1>=P2

when P1=P2=0

 

The output is on whenever
the outlet pressure is
greater than P1 but less
than P2.

 

The output comes on once
the outlet pressure
reaches P1. The output
will remain on until the
outlet pressure drops to
P2.

 

The output is on whenever
the outlet pressure equals
the commanded pressure.
The output is off whenever
the input signal changes.

E

RROR 

M

ESSAGES

Summary of Contents for ITV2000 series

Page 1: ...UIDE Page 1 last updated 11 03 03 10 05 AM MICROPROCESSOR CONTROLLED E P REGULATOR ITV2000 CONTENTS 1 LAYOUT IDENTIFICATION 2 WIRING 3 INPUT SIGNAL 4 KEY LOCK FUNCTION 5 SET POINT PROGRAMMING 6 ADJUST...

Page 2: ...E Page 2 last updated 11 03 03 10 05 AM LAYOUT IDENTIFICATION WIRING Please be careful when connecting the four cable wires Improper wiring will damage the internal circuitry PIN WIRE COLOR DESCRIPTIO...

Page 3: ...e ITV has a key lock feature allowing the user to disable the setting keys This is helpful in preventing unauthorized setting changes By default the keys are locked when power is turned on The keys mu...

Page 4: ...THE MINIMUM PRESSURE F_1 Press the UP and DOWN keys until the display shows the desired minimum pressure Press and release the SET key to continue to the next step 3 SET THE MAXIMUM PRESSURE F_2 Press...

Page 5: ...minimum pressure zero adjust maximum pressure span adjust MONITOR OUTPUT The ITV is available with one of three different monitor output signals ANALOG ITV20 1 Linear analog pressure monitor signal 1...

Page 6: ...e UP and DOWN keys for 3 seconds or longer to reset SPECIFICATIONS Supply Pressure set pressure 14 5psi to 145psi 1 Output Pressure 0 725 14 5psi ITV201 0 725 72 5psi ITV203 0 725 130 5psi ITV205 Maxi...

Page 7: ...62 FAX 80a 222 5221 SMC PneumaticsInc Rochester 245 SummitPointDrive Henrietta NY 14467 Tel 716 321 1300 FAX 716 321 1865 SMC Pneumaticslnc S F 85 NicholsonLane SanJose CA 95134 Tel 408 943 9600 FAX 4...

Reviews: