Specifications
Product No.
ISE70
ISE71
Applicable fluid
Air, non-corrosive gas and non-flammable gas
Pre
s
s
u
re
s
p
e
c
.
Rated pressure range
0 to 1.000 MPa
0 to 1.600 MPa
Display/set pressure range
-0.105 to 1.050 MPa
-0.105 to 1.680 MPa
Display/min. set unit
0.001 MPa
Proof pressure
1.5 MPa
2.4 MPa
El
e
c
tr
ic
s
p
e
c
.
Po
wer
s
u
p
p
ly
v
o
lt
a
g
e
Used as switch output device
12 to 24 VDC ±10% with 10% voltage ripple or less (p-p)
Used as IO-Link device
18 to 30 VDC, including ripple (p-p) 10%
Current consumption
35 mA or less
Protection
Polarity protection
Ac
c
u
ra
c
y
Display accuracy
±2%F.S.±1 digit (at ambient temperature 25±3
o
C)
Repeatability
±0.5%F.S.
Temperature characteristics
±2%F.S. (25
o
C standard)
Swit
c
h
o
u
tp
u
t
Output type
Select from NPN or PNP open collector output.
Output mode
Select from hysteresis mode, window comparator mode,
error output or switch output OFF.
Switch operation
Select from normal output or reversed output.
Maximum load current
80 mA
Maximum applied voltage
30 V (during NPN output)
Internal voltage drop
(Residual voltage)
1.5 V or less (Load current 80 mA)
Delay time
1
1.5 ms or less
(delay time available for anti-chattering function:
Variable at 0 to 60 s/0.01 step)
Hy
s
te
re
s
is
Hysteresis mode
Variable from 0
2
Window comparator mode
Short circuit protection
Provided
Dis
p
la
y
Unit
3
MPa, kPa, kgf/cm
2
, bar, psi
Display type
LCD
Number of displays
3-screen display (Main display, sub display x 2)
Display colour
Main display: Red/Green, Sub display: Orange
Number of display digits
Main display: 4 digits (7-segments)
Sub display: 4 digits (Upper 1 digit 11-segments, 7-segments for other)
Operation light
LED is ON when switch output is ON (OUT1, OUT2: Orange)
Digital filter
4
Variable at 0 to 30 s/0.01 step