Installation and Maintenance Manual
IS3000 Series Pressure Switch

This Manual should be read in conjunction with the current product catalogue

For future reference, please keep this manual in a safe place

Safety Instructions

These safety instructions are intended to prevent a hazardous situa-
tion and/or equipment damage.These instructions indicate the level
of potential hazard by label of “Caution”, “Warning” or “Danger”.
To ensure safety, be sure to observe ISO4414 

(Note1)

, JIS B 8370 

(Note2)

and other safety practices.
Note 1: ISO 4414: Pneumatic fluid power – Recommendations for the
application of equipment to transmission and control systems.
Note 2: JIS B 8370: Pneumatic system axiom.

CAUTION :

Operator error could result in injury or

equipment damage.

WARNING:

Operator error could result in serious

injury or loss of life.

DANGER :

In extreme conditions, there is a 

possible result of serious injury or loss of life.

WARNING

1. The compatibility of pneumatic equipment is the respon-

sibility of the person who designs the pneumatic system
or decides its specifications.

Since the products specified here are used in various operating
conditions, their compatibility for the specific pneumatic system
must be based on specifications or after analysis and/or tests to
meet your specific requirements.

2. Only trained personnel should operate pneumatically

operated machinery and equipment.

Compressed air can be dangerous if an operator is unfamiliar 
with it. Assembly, handling or repair of pneumatic systems should
be performed by trained and experienced operators.

3. Do not service machinery/equipment or attempt to

remove component until safety is confirmed.

1)  Inspection and maintenance of machinery/equipment should

only be performed after confirmation of safe locked-out 
control positions.

2)  When equipment is to be removed, confirm the safety process

as mentioned above. Switch off air and electrical supplies and
exhaust all residual compressed air in the system.

3)  Before machinery/equipment is re-started, ensure all safety

measures to prevent sudden movement of cylinders etc.
(Bleed air into the system gradually to create back-pressure,
i.e. incorporate a soft-start valve).

4. Contact SMC if the product is to be used in any of the 

following conditions:

1)  Conditions and environments beyond the given specifica-

tions, or if product is used outdoors.

2)  Installations in conjunction with atomic energy, railway, air

navigation, vehicles, medical equipment, food and beverage,
recreation equipment, emergency stop circuits, press 
applications, or safety equipment.

3)  An application which has the possibility of having negative

effects on people, property, or animals, requiring special 
safety analysis.

CAUTION

Ensure that the air supply system is filtered to 5 micron.

Specifications

Fluid

Air

Proof pressure

1 MPa (10.2 kgf/cm

2

)

Max. operating pressure

0.8 MPa (8.2 kgf/cm

2

)

Pressure adjustable range

0.1 to 0.7 MPa (1 to 7.1 kgf/cm

2

)

Ambient and fluid temperature

-5 to +60°C (No freezing)

Contact configuration

1ab

Hysteresis

0.05 MPa (0.51 kgf/cm

2

) or less

Repeatability

±0.05MPa {±0.5 kgf/cm

2

}

Weight

0.15 kg

Microswitch rating

Model

IS3*00

IS3*10

Load

Non-inductive load (A)

Inductive load (A)

Non-inductive 

load (A)

Resistance load

Lamp load

Inductive load

Motor load

Motor load

N.C.

N.O.

N.C.

N.O.

N.C.

N.O.

N.C.

N.O.

N.C.

N.O.

AC125

5

1.5

0.7

3

2.5

1.3

0.1

AC250

3

1

0.5

2

1.5

0.8

-

DC30

4

2

3

3

0.1

DC125

0.4

0.05

0.4

0.05

-

Installation

WARNING

1. Ensure all air and power supplies are ISOLATED before 

commencing installation.

2. DO NOT install this product in an explosive atmosphere.
3. Protect from oil and water splashes.
4. If it is intended to energise this product for extended periods of

time please consult SMC.

5. Protect the air supply from freezing.
6. Operate within the specified pressure and temperature ranges.
7. DO NOT subject the unit to impact or vibration.
8. DO NOT install in environments containing corrosive gasses.

Wiring (Fig 1)

Ensure that the microswitch is wired in accordance with the diagram
shown in Fig 1.

Wiring indicator lamp OFF (pressure rise) (Fig 2)

To wire the indicator lamp to go “OFF” on detecting a pressure rise,
both the A and B contacts must be wired in accordance with the 
diagram shown in Fig 2.

Wiring indicator lamp ON (pressure rise) (Fig 3)

To wire the indicator lamp to come “0N” on detecting a pressure rise,
only the B contact is wired in accordance with the diagram shown in
Fig 3.

CAUTION

Two adhesive nameplates are supplied to indicate the above 
situations, place the appropriate label on the outside of the unit in a
highly VISIBLE position.
There are (+) AND (-) terminals for connecting a 24VDC power supply.
The red lead wire connects to the (+) terminal and the black lead wire
to the (-) terminal. A LED is fitted to the 24VDC supply. The LEAKAGE
current is 3mA.

Operating a PLC using leakage current (Fig 4)

Directly connect the LED to the power supply as shown in Fig 4.

Internal resistance of the lamp is L1: 33k

, L2: 100k

, and L5:

8.2k

.

Adjustment

The pressure can be set by turning the adjusting screw, using a small
bladed screwdriver.

Maintenance

WARNING

Before carrying out any maintenance work ensure all air and power
supplies are ISOLATED.

Please consult SMC before dismantling this product.

074A/Eng

When you enquire about the product, please contact the following 

SMC Corporation

:

ENGLAND

Phone 01908-563888

TURKEY

Phone 212-2211512

ITALY

Phone 02-92711

GERMANY

Phone 6103-402-0

HOLLAND

Phone 020-5318888

FRANCE

Phone 01-64-76-10-00

SWITZERLAND

Phone 052-396 31 31

SWEDEN

Phone 08-603 07 00

SPAIN

Phone 945-184100

AUSTRIA

Phone 02262-62-280

Phone 902-255255

IRELAND

Phone 01-4501822

GREECE

Phone 01-3426076

DENMARK

Phone 70 25 29 00

FINLAND

Phone 09-68 10 21

NORWAY

Phone 67-12 90 20

BELGIUM

Phone 03-3551464

POLAND

Phone 48-22-6131847

PORTUGAL

Phone 02-610 8922

Normally

closed/

open

Rated 
voltage (V)

Fig 1

Fig 2

Neon lamp lights OFF
by pressure increase

Fig 3

Fig 4

Neon lamp lights ON
by pressure increase

Model

Piping method

Microswitch type

Microswitch min.

applicable load

IS3000-02

1/4 screw joint type

Standard type

5 VDC, 160 mA

IS3000-02L*
IS3100

Gasket mounted type

IS3100-L*
IS3010-02

1/4 screw joint type

Micro load type

5 VDC, 1mA

IS3010-02L*
IS3110

Gasket mounted type

IS3110-LX