10. Specification for Option M
10- 2
10.3
Installation of motor type auto drain
1) Hold the hexagon-head part (width across flats: 32) at port Rc1/2 of the air dryer with spanner.
Then install nipple, ball valve (width across flats: 25).
Note 1) Put up the seal tape or the sealant to the nipple. Torque R1/2: 28 to 30Nm
2) Hold the ball valve with the spanner. Then install a nipple and a motor type auto drain.
Install with “out port" down in a vertical position. Inclination from the vertical line should be less than 5°.
3) Install one-touch fitting (width across flats: 17) to drain port (width across flats: 30) and the drain tube.
4) Connect the 2 electric cables coming out from the auto drain with the two electric cables from the dryer
unit. Insert the drip-proof connector to the deepest part.