HRX-MM-N007
Chapter 4 Service Procedure
4.5 Replacement Procedure
HRS Series
4-40
Be sure to shut off the breaker of the facility power supply (the user’s
machine power supply) before replacement work.
4.5.12 Replacement of tank (For automatic water fill)
<
HRS
-A/W-
>
Table 4-19 Part number of service parts (Tank)
Description
Part number
Tank (For automatic water fill)
HRS-S0072
Removal
1.
Discharge the circulating fluid referring the 4.2.2 Discharge of the circulating fluid and
facility water.
2.
Remove the upper panel, the panels on both sides and the front panel referring the 4.2.1
Removal and the mounting of the panel.
3.
Remove the hose clamp and remove hoses. (4 pcs.)
4.
Remove the level switch pin [LS1] (two red lines) from the main board.
[Tips]
Use “57031-6000” of MOLEX for removing.
Our part no.
:
HRS-S0056
5.
Remove the
tank.
Fig. 4.5-25 Removal of tank
4.
Remove
the
pin
Tank lid
3.
Hose
Grommet
Main board
5.
Tank
Hose clamp
3.